Version 5006-0
5006-1
Output
4 to 20 mA
Permissible load
R
B
=
U
S
– 12 V
20 mA
Output current circuit
Intrinsically safe (Media 6 w. LCD/ LED)
see PTB 00 ATEX 2074 in appendix
Supply voltage U
B
two-wire transmitter
12 to 36 V DC
12 to 28 V DC only in combination
with an intrinsically safe circuit
Permissible ambient temperature
– 40 to + 70 °C
T6 max. + 60 °C
T5 max. + 70 °C
Permissible storage temperature
–40 to +80 °C
Degree of protection
IP 65 acc. to DIN VDE 0470 or EN 60529
Materials
Version
Standard version
Enclosure
Cu Zn 40 Pb
CrNi steel
Measuring diaphragm and seals
ECO/NBR (other materials on request)
Measuring springs
CrNi steel
Diaphragm plates and function. parts
Lever
Indicating unit
Polycarbonate, polyamide
Note!
Devices intended for oxygen service are labeled
"Oxygen! Keep free of oil and grease!"
These versions are cleaned and assembled by the manufacturer under special conditions.
Appropriate gloves need to be worn on replacing parts that come into contact with oxygen,
e.g. measuring springs.
When returning devices designed for oxygen service to the manufacturer for repair, the sen-
der assumes full responsibility that the handling of the devices to be repaired meets the re-
quirements specified in VBG 62 or equivalent regulations until the devices are handed over
to the manufacturer. Otherwise, SAMSON AG will not accept any responsibility.
EB 9527-1 EN
9
Technical data
Содержание 5006-0
Страница 5: ...Previous version New version EB 9527 1 EN 5...
Страница 30: ...30 EB 9527 1 EN...
Страница 31: ...EB 9527 1 EN 31...
Страница 32: ...32 EB 9527 1 EN...
Страница 33: ...EB 9527 1 EN 33...