Release key, 0 mbar appears in the
display. Current signal I = 4 mA.
Activate the write protection: turn switch
4
ON
.
Correction when the tank is filled
If the differential pressure lines are
equipped with shut-off and equalizing
valves, zero can be checked even when the
plant is in operation.
To achieve this, place the valve block or
equalizing valve in the test position to ob-
tain the same pressure in both measuring
chambers.
1. Close the shut-off valve in the high-
pressure line.
2. Open the equalizing valve or bypass in
the valve block.
3. Close the shut-off valve in the low-
pressure line.
The valve block is in test position!
Write protection: turn switch
4
OFF
.
Press
and
hold down
key.
ZERO
and
X,X
mbar appear in the display.
Current signal I indicates the present
mA value.
Press key. Zero is adjusted.
Release
key, 0 mbar appears in the
display.
Current signal I = 4 mA corresponding to
the liquid level at 0 mbar differential
pressure.
(See note on gas column correction on page 17.)
Activate the write protection:
turn switch
4
ON
.
Return valve block or equalizing valve to
operating position:
1. Open the shut-off valve in the low-
pressure line.
2. Close equalizing valve.
3. Open the shut-off valve in the high-
pressure line.
Fig. 9
⋅
Test arrangement
0
20
40
60
80
100
%
m
3
x1000
– +
Off
.
~
–
+
–
+
Supply air reducing station
with oil filter and pressure
gauge
Power
supply
Supply unit
Ammeter
Precision regulator with pressure gauge Cl. 0.1
Test pressure
Use air free of oil or other gases,
e.g. N
2
, only
Caution!
For devices used to measure
oxygen
, the test medium must be
free of oil
and grease!
18
EB 9527-1 EN
Setting