66 | SAMLEX AMERICA INC.
SECTION 10 |
Specifications
Product Highlights
Model no.
Power
rating*
input Connections
Circuit Breaker
"Charger"
Circuit Breaker
"load"
Output Connections
G4-2012A
2000 vA
•
Terminal Block, 65A for AC input
•
M8 stud and nut for DC input
•
M8 thumb nut for external
charger input
40A
30A
Terminal Block, 65A
for AC output
G4-2524A
2500 vA
40A
35A
G4-3524A
3500 vA
60A
40A
* Power rating is shown as Apparent Power in volt Amp (vA). Active Power in Watts will be controlled by the Power Factor of the AC side load i.e.
Active Power in Watts = Apparent Power in vA x Power Factor (normally ranges from 0.5 to 1). For resistive type of loads with Power Factor of 0.9
to 1, the Apparent Power in vA will be almost equal to the Active Power in Watts.
Utility / Generator Pass Through (bypass) Mode - external AC Line Input Is Available
Parameter
g4-2012a
g4-2524a
g4-3524a
Input voltage Waveform
Pure Sine Wave
Input voltage range
120 vAC nominal (80 vAC to 140 vAC ± 4%)
Input voltage: Low Line Disconnect
Programmable: 80 vAC to 95 vAC ± 4%
Input voltage: Low Line Re-connect
10v higher than programmed value of Low Line Disconnect
Input voltage: High Line Disconnect
Programmable:130 vAC to 140 vAC ± 4%
Input voltage: High Line Re-
connect
5 v lower than the programmed value of High Line Disconnect
Nominal Input Frequency
50Hz / 60Hz ( Auto detection )
Default: 60Hz for 120v version
Low Frequency Disconnect
57 ± 0.3Hz for 60Hz / 47 ± 0.3Hz for 50Hz
Low Frequency Re-connect
58 ± 0.3Hz for 60Hz / 48 ± 0.3Hz for 50Hz
High Frequency Disconnect
65 ± 0.3Hz for 60Hz / 55 ± 0.3Hz for 50Hz
High Frequency Re-connect
64 ± 0.3Hz for 60Hz / 54 ± 0.3Hz for 50Hz
Maximum AC Input Current
40A, limited by Circuit Breaker
marked “Charger”
40A, limited by Circuit Breaker
marked “Charger”
60A, limited by Circuit Breaker
marked “Charger”
Output voltage Waveform
Same as waveform of Line input voltage
Output Overload and Short Circuit
Protections
40A Circuit Breaker marked
“Charger”
40A Circuit Breaker marked
“Charger”
60A Circuit Breaker marked
“Charger”
Efficiency (Pass Through / Bypass
Condition)
> 95% (When battery is fully charged)
Transfer Relay Rating
•
80A, 277 vAC (Two 40A relays in parallel) for the Line side (120v version)
•
80A, 277 vAC (Two 40A relays in parallel) for Neutral side for Neutral to Chassis Ground switching
Transfer Time (Utility / Generator
to Inverter )
20 ms (Typical)
Minimum DC Input voltage
for Pass Through (Bypass) and
Charging
9v
18v
18v
Maximum Pass Through (Bypass)
Overload Current
40A for G4-2012A
40A for G4-2524A
60A for G4-3524A