SECTION 5 |
Installation
K1, K4 Relays (in parallel) for Hot Switching
K2, K3 Relays (in parallel) for Neutral to
Ground Bond Switching
3, 4
Normally closed contacts
4-5
Normally open contacts
NOTE:
Relays K1 to K4 are de-energized in
Inverter Mode and are energized in
Utility / Generator Mode
628-2011_G4-TransferRelay_Aug2011
NEUTRAL
BI-DIRECTIONAL
TRANSFORMER
HOT
K2
K3
K1
K4
METAL CHASSIS
OF THE UNIT
HOT
IN
HOT
OUT
NEU
OUT
GND
OUT
GND
IN
NEU
IN
3
4
5
3
4 5
3
4 5
3
4
5
INVERTING
CHARGING
Fig. 5.10 Operation of Transfer Relay and Neutral to Ground Bond switching in G4 series