44 | SAMLEX AMERICA INC.
SAMLEX AMERICA INC. | 45
Earth Ground through the Neutral to Earth Ground bond in the AC Breaker Panel/
Load Center supplying Grid power / AC output connections of the generator.
• Disabling Neutral to Ground Bond
: In some applications, the Output Neutral
may be required to remain isolated from chassis/Ground at all times. For this,
automatic Output Neutral to chassis Ground bond can be disabled by disconnecting
the Insulated Male/Female Quick Disconnect [27, Fig 3.9.2(a)] located in the AC
Wiring Compartment in EVO-1212F-HW/1224F-HW.
In EVO-1212F/1224F, this
Insulated Male/Female Quick Disconnect is accessible after opening the top
cover of the unit.
• System grounding, as required by National / Local Electrical Codes / Standards, is
the responsibility of the user / system installer.
For further details please refer to Sections 4.4.1 / 4.4.2 and Fig 4.1.
MISE EN GARDE!
•
En état de défaut, le neutre de la sortie CA de l’unité dans le “Mode de l’onduleur / décharge” obtient
lié au châssis métallique de l’unité à travers la interne “Neutre à châssis relais de commutation” (RY2 Relais
de la figure 4.1)
•
Dans “Mode de chargement”, l’interne “Neutre à châssis relais de commutation - RY2” déconnecte le
neutre de la connexion de sortie AC du châssis de l’unité. Le neutre de la connexion de sortie CA de l’unité
va obtenir lié à la terre des masses à travers le neutre à la terre liaison au sol dans le centre de panneau de
disjoncteurs AC / charge alimenter Grille / connexions de sortie CA du générateur.
•
Désactivation du lien neutre à mise a terre:
Dans certaines applications, il est nécessaire que la
sortie neutre soit isolé du châssis/mise a terre à tout moment. Pour cela, la production automatique de
la position neutre à la masse du châssis bon peut être désactivé en déconnectant le mâle/femelle isolée
[Déconnexion rapide, 27 Fig 3.9.2(a)] situé dans le compartiment de câblage AC dans
EVO-1212F-
HW/1224F-HW. Dans EVO-1212F/1224F, ce mâle/femelle isolée est accessible à déconnexion
rapide après l'ouverture du capot de l'unité.
•
Mise à la terre du système, tel que requis par la National / codes électriques locaux / normes, est de la
responsabilité de l’installateur utilisateur / système.
3.6.4 AC Input Considerations – Voltage And Frequency
The EVO
TM
unit is designed to accept 120 VAC, 60 Hz single phase AC power from Grid or from
good quality Generator with stable 120 VAC / 60 Hz output. These 120V versions come preset
for 60 Hz operation.
3.6.5 Preventing Paralleling of the AC Output
WARNING!
The AC output of the unit cannot be synchronized with another AC source and hence, it
is not suitable for paralleling on the output side. The AC output of the unit should never
be connected directly to an electrical breaker panel / load center which is also fed from
another AC source. Such a connection may result in parallel operation of different power
sources and AC power from the other AC source will be fed back into the unit which
will instantly damage the output section of the unit and may also pose a fire and safety
hazard. If an electrical breaker panel / load center is fed from this unit and this panel is
also required to be powered from additional alternate AC source, the AC power from the