34
SALICRU
GENERAL_ALARM_NC
GENERAL_ALARM_NO
GENERAL_ALARM_
GND
J9
Fig. 46.
Diagram of the relay interface of integrated
warnings.
Port
Name
Function
J9-1
ALARM_NC
Normally closed (NC) contact, GENERAL
ALARM relay interface signal
J9-2
ALARM_NO
Normally open (NO) contact, GENERAL ALARM
relay interface signal
J9-3
GND
Common for GENERAL ALARM relay interface
signal
Tab. 13.
General description of the relay interface of
general alarms.
Output relay interface for mains failure warnings
The default function of port J10 is to present mains failure
warnings. When there is a mains failure, the system sends a
mains failure warning and an auxiliary relay interface signal
is generated. A diagram of the ports is shown in Fig. 47 and a
description in Tab. 7.
UTILITY_F
AIL_NC
UTILITY_F
AIL_NO
UTILITY_F
AIL_GND
J10
Fig. 47.
Diagram of the relay interface of mains failure
warnings.
Port
Name
Function
J10-1
UTI_FAIL_NC
Normally closed (NC) contact, AC MAINS
FAILURE relay interface signal
J10-2
UTI_FAIL_NO
Normally open (NO) contact, AC MAINS
FAILURE relay interface signal
J10-3
GND
Common for AC MAINS FAILURE relay interface
signal
Tab. 14.
Description of the relay interface of mains failure
warnings.
5.3.4.2. Communications interface.
The RS-232, RS-485 and USB ports provide data that can be
used by authorised personnel for startup and maintenance.
They can also be used in the battery room for integrated or
network monitoring systems.
The SNMP port (optional) is used for communications in the
on-site installation.
The smart slot interface (optional) is an additional relay
interface.
Содержание SLC ADAPT Series
Страница 1: ...SLC serie ADAPT 180 300 y 500 kVA UNINTERRUPTIBLE POWER SUPPLY UPS USER S MANUAL...
Страница 10: ...10 SALICRU Fig 6 Front and rear view of 10 slot cabinet 300 kVA 200 kVA at 3x208 V with closed doors...
Страница 12: ...12 SALICRU Fig 8 Front view of 10 slot cabinet 500 kVA 300 kVA at 3x208 V with closed doors...
Страница 64: ...64 SALICRU...
Страница 65: ...65 SLC ADAPT UNINTERRUPTIBLE POWER SUPPLY UPS USER S MANUAL...