Salicru SLC ADAPT Series Скачать руководство пользователя страница 18

18

SALICRU

Fig. 14

 shows, byway of example, a single-line diagram of the 

device with three-phase input and output.

All modules in the cabinet are structured according to the same 

criteria, terminals for the power supply of the PFC rectifier and 

independent static bypass, and input, output, static bypass 

and manual bypass disconnectors. However, unless otherwise 

requested, for separate networks originally from the factory, 

the terminals of the phases of both blocks are connected by 

means of strips to provide a single common input.

When separate power supplies are required, it is 

obligatory to remove the strips between the phases of 

both blocks before connecting the power cables, leaving the 

connection strip of the neutral terminals.

4.3.2.1.  Power modules (PM).

Power modules are the basic core of the entire 

SLC ADAPT

 

system. Apart from the static bypass block and LCD touch 

screen, each power module contains all of the converters and 

functionalities of a traditional UPS. Since this device consists 

of a number of variable modules depending on the cabinet 

used, a multi-parallel system is obtained with the behaviour 

equivalent to that of a single mono-bloc UPS and the advan-

tages of a modular UPS.

The system supplies power to the critical load (such as com-

munication and data processing equipment) with uninterrupted 

high quality AC power. The power supplied by the unit is stable, 

without voltage and/or frequency variations and free from 

other disturbances such as cuts or micro-cuts, sine wave al-

terations, electrical noise, anomalies commonly present in the 

commercial AC network.

This is achieved through the double-conversion high frequency 

Pulse Width Modulation (PWM), in combination with a digital 

control based on a Digital Signal Processor (DSP), which pro-

vides high reliability and availability.

As can be seen in 

Fig. 14

, the AC power supplied to the UPS 

input is converted into DC voltage. This voltage supplies a con-

verter that transforms the voltage type from DC to AC, clean of 

disturbances and variations of the AC input mains. If this fails, 

the PFC rectifier changes the input source of the AC mains to 

that of the batteries, powering in the same way through the 

output of the UPS to the load for a limited time, that of the 

backup determined by the battery pack.

4.3.2.1.1.  Available power ratings.

The SLC ADAPT series has two different power modules, 30 

and 50 kVA, as can be seen in Fig. 2, Fig. 4, Fig. 10 and Fig. 12. 

4.3.2.2.  Static bypass.

Static transfer switch.

In the event of inverter failure, overload or overtemperature, 

the voltage connected to the static bypass line can supply 

power to the load connected to the UPS output.

The static bypass module identified in 

Fig. 14

 contains the 

power management and control circuits that allow the most 

optimum decision in each scenario to be made, in order to se-

lect the most favourable power to the critical load connected 

to the output of the UPS, either from the inverter or from the 

static bypass itself.

During normal system operation, the load is connected to the 

inverter and in case of overload or failure, it will automatically 

transfer to the static bypass line. In order to provide a clean 

transfer (without interruption) between the inverter output and 

the bypass line, they must be fully synchronized during normal 

operation. This is achieved through real-time digital control of 

the inverter, so that the frequency of the inverter follows the 

frequency of the bypass line if the bypass is within the range of 

acceptable frequencies.

In addition, a Manual Bypass, which is very useful during periods 

of maintenance or failure, is included and allows continuous 

powering of the critical load while the UPS is out of service.

When the UPS is operating in bypass mode (over static 

bypass), connected devices are not protected against 

power cuts or micro-cuts, overvoltages, voltage and/or fre-

quency variations as they are powered directly from the AC 

mains.

4.3.2.3.  Extra charger modules for 180 and 300 kVA devices.

The smart charging module is designed to supply the necessary 

charging current for long backup applications. The module is hot 

swappable and has the same size and appearance of any power 

module, supplying an adjustable current of between 0 and 50 A.

On the front, they have a high resolution LCD where the user 

can monitor the different load parameters in real time. 

The modules are designed to be inserted in 6- and 10-slot 

cabinets with only 30 kVA modules - 180 and 300 kVA devices 

- and can be inserted in the necessary number to meet battery 

charging needs. 

4.3.2.3.1.  Wiring diagram.
As can be seen in the diagram in Fig. 15, the charger modules 

are connected in parallel to the power modules. The total cur-

rent of the system is the sum of the current supplied by the 

power modules and the charger modules. 

Содержание SLC ADAPT Series

Страница 1: ...SLC serie ADAPT 180 300 y 500 kVA UNINTERRUPTIBLE POWER SUPPLY UPS USER S MANUAL...

Страница 2: ...Unpackingandtransportationtothesite 5 1 3 1 Unpackingthepowermodule 5 1 4 Siting immobilisingandconsiderations 5 1 5 Roomforthebatteries 5 2 CABINETPOSITIONING 5 2 1 180to300kVAdevices 5 2 2 500kVAdev...

Страница 3: ...hscreen 7 3 MAINMENU 7 3 1 Cabinet 7 3 2 Powermodule 7 3 3 Settings 7 3 3 1 Date Timesetting 7 3 3 2 Languagesetting 7 3 3 3 Communicationsprotocolsetting 7 3 3 4 Usersettings 7 3 3 5 Batterysettings...

Страница 4: ...ied personnel Although no effort has been spared to ensure that the in formation in this user manual is complete and accurate we accept no liability for any errors or omissions that may exist The imag...

Страница 5: ...nd startup operations to be performed in a simple and organised manner without any doubts whatsoever Finally once the equipment is installed and operating it is recommended to save the documentation d...

Страница 6: ...ments for UPSs used in areas accessible to operators EN50091 1 1 IEC62040 1 1 AS 62040 1 1 Electromagnetic compatibility EMC requirements for UPSs EN50091 2 IEC62040 2 AS 62040 2 C3 Method for specify...

Страница 7: ...ot 300 kVA and 500 kVA devices Because the product is constantly evolving however slight discrepancies or contradictions may arise If in any doubt the labelling on the device itself will always prevai...

Страница 8: ...8 SALICRU 19 8 LCD 4 98 Fig 2 Front view of 30 kVA module 20 kVA for 3x208 V AC voltages Touch display Fig 3 Front and rear view of 6 slot cabinet 180 kVA 120 kVA at 3x208 V with closed doors...

Страница 9: ...pass marking Free slot for Bypass module Bypass input A B C N Output A B C N Input A B C N Batteries N SPD option Relay interface Communications interface Power module connector Fig 5 Front and rear v...

Страница 10: ...10 SALICRU Fig 6 Front and rear view of 10 slot cabinet 300 kVA 200 kVA at 3x208 V with closed doors...

Страница 11: ...marking SPD option Relay interface Module display Free slot for Bypass module Communications interface 30 kVA power modules Power module connector Fig 7 Front and rear view of 10 slot cabinet 300 kVA...

Страница 12: ...12 SALICRU Fig 8 Front view of 10 slot cabinet 500 kVA 300 kVA at 3x208 V with closed doors...

Страница 13: ...13 Fig 9 Rear view of 10 slot cabinet 500 kVA 300 kVA at 3x208 V with closed doors SLC ADAPT UNINTERRUPTIBLE POWER SUPPLY UPS USER S MANUAL...

Страница 14: ...ut UPS output Manual bypass Cold Start Module display Bypass module 50 kVA power modules Communications interface UPS input disconnector UPS output disconnector Manual Bypass disconnector Bypass input...

Страница 15: ...0 kVA module 30 kVA for 3x208 V AC voltages Bypass input A B C Input A B C N Output A B C N Batteries N PE Fig 13 Rear view of 10 slot cabinet 500 kVA with open doors SLC ADAPT UNINTERRUPTIBLE POWER S...

Страница 16: ...tem will be indicated 0 Devices prepared for standard backups B1 Subrack cabinet with external batteries S Ambient temperature sensor C Subrack mounted on box type BATT MOD batteries supplied factory...

Страница 17: ...y charger modules are available to be installed solely with the 30 kVA SLC ADAPT modules As many charging modules as considered appropriate can be installed but this will be to the detriment of the to...

Страница 18: ...ailable power ratings The SLC ADAPT series has two different power modules 30 and 50 kVA as can be seen in Fig 2 Fig 4 Fig 10 and Fig 12 4 3 2 2 Static bypass Static transfer switch In the event of in...

Страница 19: ...float or quick voltage PFC rectifier AC DC BAT DC DC DC Battery Charger Inverter DC AC Static bypass Manual bypass Batteries AC input Bypass AC input Rectifier AC output Connection strips between pha...

Страница 20: ...terminals version B are live even if all modules are switched off It is recommended in this operating mode Remove the fastening screws of all power control and bypass modules Slightly pull the handle...

Страница 21: ...ity Weight 180 kVA 374 kg 300 kVA 560 kg 500 kVA 1350 kg Tab 1 Weight of the UPS including power modules 5 1 1 Reception unpacking and contents Reception Check that The data on the label affixed to th...

Страница 22: ...e treated as individual device for battery recharging and there fore no additional connection is required 5 1 3 Unpacking and transportation to the site The packaging of the device consists of wooden...

Страница 23: ...n system to force the cooling air flow The modules are equipped with three internal speed regu lated fans The air flow is channelled from the front to the rear Do not block the ventilation holes or ob...

Страница 24: ...t and the other by means of anchor bolts for its final permanent installation 55 86 5 349 55 86 5 10 971 10 55 522 55 47 105 687 Front door Back door Front door Rear door Anchor bolt L shaped plates W...

Страница 25: ...attery branch The voltage at the battery terminals is greater than 200 V DC Follow the safety instructions to avoid electric shock Make sure that the positive negative and neutral are cor rectly conne...

Страница 26: ...ing a sequence from bottom upwards to prevent dangerous tilting of the cabinet due to the high centre of gravity The steps to install the power modules are as follows taking as an example a 10 slot ca...

Страница 27: ...the cabinet can be made from the top or bottom Regarding the 10 slot cabinet the upper cable entry is standard while the entry at the bottom requires optional parts to be added The different cable en...

Страница 28: ...entry for 500 kVA devices Cable entry can be made from the top or bottom Fig 36 10 slot cabinet installation with cable entry at the top rear view Fig 37 10 slot cabinet installation with cable entry...

Страница 29: ...power cable connectors Type Port Connection Bolt Tightening torque 180 kVA 300 kVA 500 kVA Input Crimped cables Ring terminal M16 96 Nm Bypass input Crimped cables Ring terminal M16 96 Nm Battery inp...

Страница 30: ...ction terminals for 500 kVA devices The operations described in this section must be per formed by electricians or qualified technical personnel If difficulties arise contact our head office or local...

Страница 31: ...as shown in Fig 39 and Fig 40 Startup from batteries Cold Start Parallel interface Smart slot SNMP card Relay interface USB RS 232 RS 485 Fig 39 Relay and communication interface of 180 and 300 kVA mo...

Страница 32: ...y interface signal J9 1 ALARM_NC Normally closed NC contact GENERAL ALARM relay interface signal J9 2 ALARM_NO Normally open NO contact GENERAL ALARM relay interface signal J9 3 GND Common for GENERAL...

Страница 33: ...Off switch J6 2 BCB_CONT Status of the BCB switch Its normally closed NC auxiliary contact can be connected between this pin and the GND J7 1 GND 24 V ground reference J7 2 BCB_ONL Not useful Not impl...

Страница 34: ...gram of the ports is shown in Fig 47 and a description in Tab 7 UTILITY_FAIL_NC UTILITY_FAIL_NO UTILITY_FAIL_GND J10 Fig 47 Diagram of the relay interface of mains failure warnings Port Name Function...

Страница 35: ...Red Load Green Bypass Green State Red Tab 16 Inverter startup 7 The UPS transfers from bypass to inverter once the inverter stabilises LED indicator states are shown in Tabla 8 Indicator State Indicat...

Страница 36: ...rom Normal mode to Bypass mode 1 Enter the Operation menu click on the transfer to bypass icon and the system will transfer to Bypass mode 2 Press the BYP button on the control panel for more than two...

Страница 37: ...Q3 then close the input circuit breaker Q1 and finally close the bypass input circuit breaker Q4 The system will start up 1 The static bypass connects 30 seconds after the display illuminates and the...

Страница 38: ...reconnect it When the EPO is tripped the load stops being powered by the UPS Pay attention when using the EPO function EPO button Fig 54 EPO button 6 6 INSTALLATION OF THE PARALLEL SYSTEM The UPS syst...

Страница 39: ...r DC AC inverter DC DC charger DC DC charger DC DC charger Battery Battery Battery Load Manual bypass Manual bypass Manual bypass MBS OS1 OS OS2 OS3 IS1 IS2 IS3 Static bypass Static bypass Static bypa...

Страница 40: ...500 kVA devices 6 6 2 Jumper settings for parallel operation The settings of the jumpers of the parallel cards will be dif ferent depending on whether it is a 2 UPS or 3 UPS system 6 6 2 1 Case of 2 U...

Страница 41: ...e parallel system 6 6 4 Connection of parallel cables The control cables for parallel operation must connect all de vices in a ring as shown in Fig 64 Fig 64 Ring parallel connection of 3 devices 6 6...

Страница 42: ...ame way always checking that the remaining capacity of the system can support the connected loads 2 Transfer from the parallel system of Normal mode to Bypass mode Taking again the example of the 3 UP...

Страница 43: ...1 sec Situation none of the above Tab 20 Status and failure combinations 7 1 2 Operation and control buttons The operation and control buttons include FUNC buttons and behaviour OFF buttons a The FUNC...

Страница 44: ...lure 113 Input current unbalanced 55 Overload 115 Overvoltage in DC bus 57 Overload time exceeded 117 Rectifier soft start failure 59 Overtemp in inverter 119 Relay open 61 Inverter inhibited 121 Rela...

Страница 45: ...ack of the door to activate it INV Long press transfer to inverter MUTE Long press to activate or deactivate the audible alarm Tab 24 Functions of the control and operation buttons When the frequency...

Страница 46: ...e Information display Operating status Submenu Version information Fig 72 Cabinet screen This menu includes the following parts title operating status version information submenu and information displ...

Страница 47: ...ent Hz Output frequency PF Power factor Loads kVA Sout Apparent power kW Pout Active power kVar Qout reactive power Load percentage of UPS load Batteries V Battery positive negative voltage A Battery...

Страница 48: ...d show the current operating status a Green indicates that the module is working normally b Black indicates that the module is invalid c Red indicates the absence or failure of the module For example...

Страница 49: ...e selected Outlet temperature C Outlet temperature of power module selected Code S Failure code For maintenance personnel Tab 26 Description of each Module submenu 7 3 3 Settings Press icon at the bot...

Страница 50: ...n 140 and 180 elements The end of backup voltage will be 360V and the highest voltage 620 V Battery capacity setting The user can adjust the capacity value of a battery element For example if the syst...

Страница 51: ...Tab 27 Current limit per power module Temperature compensation setting This setting is optional and requires the connection of an NTC temperature sensor to contact J2 The UPS will adjust the charging...

Страница 52: ...battery If N Cpm 0 2C the extra charger module charging cur rent setting should not exceed 0 2C Ccm M Service settings The user can select the system s work mode If the system is configured in parall...

Страница 53: ...e configured by the startup per sonnel c For the Batteries and Service options a second level authentication is necessary and the settings must be configured by the personnel responsible for device op...

Страница 54: ...wn Bypass fan failure 20 Bypass module overload Bypass current above pre set limit If bypass current below 135 of rated current only one alarm is generated in UPS 21 Bypass overload Tout Overload stat...

Страница 55: ...out 39 UPS inhibition Prevents system from transferring from bypass to UPS inverter Check 1 If capacity of power module is sufficient for load 2 If rectifier is ready 3 If bypass voltage is normal 40...

Страница 56: ...imit Check 1 If rectifier diodes are damaged 2 If PFC or IGBT are damaged 3 If PFC diodes are broken 4 If SCR or IGBT drivers are abnormal 5 If soft start resistors or relays are abnormal 72 Relay con...

Страница 57: ...there is an event and it has been deleted Yellow there is a warning Red there is a failure 7 3 5 Operate menu Press icon at the bottom of the screen to access the Operate menu Fig 88 Operation menu Th...

Страница 58: ...tem enters the Charts menu Fig 89 Charts menu Users can see the output voltage output current and bypass voltage waveforms by touching the corresponding icon on the left side of the interface The size...

Страница 59: ...hem to the cabinet structure 2 Once maintenance is finished reinsert the modules and tighten the fixing screws 3 Transfer the UPS from maintenance Bypass mode to Normal mode see chapter 6 3 5 8 4 BATT...

Страница 60: ...regulatory procedures for the intervention of T S S in the event of a fault 8 6 2 Exclusions The company will not be bound by the warranty if the defect in the product is considered to not exist or t...

Страница 61: ...2 x 22 2 x 11 MODEL SLC ADAPT TECHNOLOGY On line double conversion three level PWM DSP control INPUT 3 x 380 400 415 V AC 3 x 208 220 V AC MODULES AVAILABLE kVA kW 30 27 50 45 20 18 30 27 Charging vo...

Страница 62: ...7 180 162 1100 x 600 x 1600 199 369 SLC 20 ADAPT 200 A 3 x 208 3 x 220 V 1 to 10 20 18 200 180 1100 x 600 x 1600 199 369 SLC 30 ADAPT 300 3 x 380 3 x 400 3 x 415 V 1 to 10 30 27 300 270 1100 x 600 x 2...

Страница 63: ...yristor a 4 layer semiconductor device that works as an almost ideal switch THD Total harmonic distortion Harmonic distortion occurs when the output signal of a system does not equal the signal that e...

Страница 64: ...64 SALICRU...

Страница 65: ...65 SLC ADAPT UNINTERRUPTIBLE POWER SUPPLY UPS USER S MANUAL...

Страница 66: ...any salicru salicru_SA Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers The Technical Serv...

Отзывы: