23
5.1.3.1. Unpacking the power module.
(Only for devices with modules packed separately.)
The steps will be as follows:
1. Gently place the module on the floor or platform.
Fig. 25.
Packed module.
2. Cut the plastic packing tapes and open the box.
1
2
1. Cardboard
2. Protective foam
Fig. 26.
Packing opening.
3. Remove the upper protective foam (Fig. 18).
1. Cardboard
2. Protective foam
3. Power module
Fig. 27.
Remove protective foam.
4. Remove the UPS module with plastic packing from the card-
board box.
ATTENTION!
Properly set aside the packing materials
for subsequent recycling according to environmental
protection regulations.
5.1.4. Siting, immobilising and considerations.
•
The UPS is intended for indoor installation. The default
protection rating is IP20. The device is cooled by forced
convection with internal fans. Ensure that there is enough
space for proper ventilation and cooling of the UPS.
•
The location will be in a ventilated room, controlled tem-
perature and humidity to maintain the device in the environ-
mental parameters within the specified operating range.
The cooling capacity of the air conditioner will be selected
according to the losses of the UPS and other devices in the
same room.
•
The room will have adequate filters to prevent environ-
ments with dust or lint from contaminating the device and
adversely affecting its proper operation or generating, as
a result, direct or indirect fire, and have strict preventative
maintenance control. This control will be more rigorous, ex-
haustive and appropriate to the circumstances, when there
may be a dusty environment with conductive materials in
suspension.
•
When the conditions of the room are extreme, it will be
necessary to install an external ventilation system to force
the cooling air flow.
•
The modules are equipped with three internal speed regu-
lated fans. The air flow is channelled from the front to the
rear. Do not block the ventilation holes or obstruct the air
circulation.
•
Keep the UPS away from water, sources of heat and flam-
mable, explosive or corrosive materials. Do not install the
UPS where there is direct sunlight, dust, volatile gases, cor-
rosive materials or high salinity.
•
Do not install the UPS in environments with conductive ma-
terials in suspension.
•
The ambient temperature for battery operation is 20 to
25°C. If the batteries operate above 25°C, their service life
will be reduced, and if they operate below 20°C, their ca-
pacity will be reduced.
•
The batteries generate small amounts of hydrogen and ox-
ygen at the end of their charging. Make sure that the loca-
tion of the batteries is ventilated with fresh air that meets
standard EN50272-2001.
•
If external batteries are installed, fit the circuit breakers
(or fuses) of the batteries as close as possible to them. The
connection cables should be as short as possible.
•
Make sure that the floor or platform where the device will
be installed supports the weight of the UPS, batteries and
battery bank.
The cabinet of the UPS, batteries and battery bank can
be installed on a concrete base or other non-combus-
tible surface that does not vibrate and has a slope of less than
5° with respect to the horizontal.
5.1.5. Room for the batteries.
•
The batteries generate quantity of hydrogen and oxygen
during the charging process, reason why it is indispensable
condition to have a good air circulation of the room.
•
The stability and ambient temperature of the room where
the battery is located is an important factor that determines
the capacity to store the energy during the chemical pro-
cess that occurs during charging. In the same way, these
SLC ADAPT
UNINTERRUPTIBLE POWER SUPPLY (UPS)
USER'S MANUAL
Содержание SLC ADAPT Series
Страница 1: ...SLC serie ADAPT 180 300 y 500 kVA UNINTERRUPTIBLE POWER SUPPLY UPS USER S MANUAL...
Страница 10: ...10 SALICRU Fig 6 Front and rear view of 10 slot cabinet 300 kVA 200 kVA at 3x208 V with closed doors...
Страница 12: ...12 SALICRU Fig 8 Front view of 10 slot cabinet 500 kVA 300 kVA at 3x208 V with closed doors...
Страница 64: ...64 SALICRU...
Страница 65: ...65 SLC ADAPT UNINTERRUPTIBLE POWER SUPPLY UPS USER S MANUAL...