background image

41

8.  MAINTENANCE, WARRANTY AND SERVICE.

8.1.  BATTERY MAINTENANCE.

 

Pay attention to any safety instructions stated in EK266*08 

manual section 1.2.3 referred to batteries.

 

The useful lifetime of the batteries depends on the ambient 

temperature and other factors like the quantity of charging 

and discharging cycles and the deep discharges done.

Its design lifetime is between 3 and 5 years if the ambient 

temperature is between 10 and 20 ºC. Under request, other 

typology and/or design lifetime batteries can be supplied.

 

The UPS from 

SLC TWIN PRO2

 series only needs a min-

imum maintenance. The used batteries in standard models 

are lead acid, sealed, VRLA and maintenance free. The only 

requirement is to charge them regularly in order to extend 

their lifetime.

Meanwhile, the UPS is connected to mains, started up or 

not, it will keep the batteries charged and will guarantee a 

protection against overcharge and over discharge.

8.1.1.  Notes to replace and install the batteries. 

 

In case of replacing any interlink wire, purchase original 

parts through the authorised distributors or service centres 

in order to avoid over heating or sparks due to the risk that 

would entail the use of not enough size.

 

Do not short both battery poles + and -, exists risk of elec-

trocution or fire.

 

Make sure that there is not any voltage before handling the 

batteries. The battery circuit is not isolated from the input, 

so dangerous voltages between battery and earth can exist.

 

Although the input circuit breaker is turned off, the internal 

parts of the UPS are still connected to the batteries, so dan-

gerous voltages are present.

So, before doing any maintenance or reparation, the in-

ternal battery fuse must be removed and/or the connectors 

between them and the own UPS too.

As the battery circuit is not isolated from the input, so dan-

gerous voltages between battery and earth or ground (any 

metallic part of the cabinet, supports and accessories in-

cluded) can exist.

 

Batteries have dangerous voltages. The maintenance and 

battery replacement must be done by qualified personnel 

and familiarized with them. No other persons must manipu-

late them.

8.2.  UPS TROUBLE SHOOTING GUIDE.

If the UPS doesn't work properly, check the information dis-

played in the LCD panel. 

Try to solve the problems by following the steps described in 

table 15. If the problem persists, consult with our Technical Ser-

vice and Support 

T.S.S.

.

When necessary contact with our Technical Service and Sup-

port 

T.S.S.

, and provide the following information:

 

UPS model and serial number.

 

Date of the problem.

 

Complete description of the problem, including the informa-

tion supplied by the LCD or leds or alarm status.

 

Power supply condition, type of load and load percentage,  

ambient temperature, cooling conditions.

 

Battery information (capacity and quantity) and if the equip-

ment is a 

(B0) or (B1)

.

 

Other informations considered as important.

8.2.1.  Troubleshooting guide.

Symptom

Possible cause

Solution

Neither alarms nor indications in the LCD panel and 

normal mains voltage. 

The input cables are not connected properly.

Check if the input cables are firmly connecte to mains. 

The 

 icon and 

  warning code blink in the 

LCD panel and the acoustic alarm beep every second.

EPO function is activated.

Close the EPO circuit to deactivate it. 

The 

 icon and 

BATT FAULT 

message blink 

in the LCD panel and the acoustic alarm beep every 

second.

The internal or external battery are not properly connected.

Check if all the batteries are properly connected.

The 

 and 

 icons blink in the LCD panel 

and the acoustic alarm beep twice every second.

The UPS is overloaded. 

Remove/shutdown the exceeding loads connected at 

the UPS output.

The UPS is overloaded. The connected devices to the 

UPS are directly supplied from mains through the internal 

Bypass.

Remove/shutdown the exceeding loads connected at 

the UPS output.

After several overloads, the UPS is blocked on Bypass 
mode. The connected devices to the UPS are supplied 

directly from mains.

First remove/shutdown the exceeding loads connected 

at the UPS output. Then shutdown the UPS and reboot 

it .

Code fault 43 is displayed. The 

 icon lights in the 

LCD panel and the acoustic alarm beeps continuously.

The UPS has been overloaded for long time and their 

equipment is blocked. The UPS is shutdown automatically.

Remove/shutdown the exceeding loads connected at 

the UPS output and reboot it.

Code fault 14 is displayed, the acoustic alarm beeps 

continously .

The UPS is automatically shutdown due a short-circuit at 

its output.

Check the output wiring and/or connected devices to 

its output are short-circuited.

SLC TWIN PRO2

 UNINTERRUPTIBLE POWER SUPPLY (UPS)

USER'S MANUAL        

Содержание 4.. 20 kVA series

Страница 1: ...SLC TWIN PRO2 4 20 kVA UNINTERRUPTIBLE POWER SUPPLY UPS USER S MANUAL...

Страница 2: ...nparts 5 2 CONNECTION 5 2 1 ConnectionoftheinputterminalstoACpowersupply 5 2 2 Connectionofload stotheoutputterminalsoroutput1 5 2 3 Connection of the load s to the output terminals 2 TWIN 3 PRO2from8...

Страница 3: ...5 OPERATINGMODES STATUSDESCRIPTION 7 6 WARNINGCODES 7 7 ERROROFAULTCODES 7 8 WARNINGINDICATORS 8 MAINTENANCE WARRANTY AND SERVICE 8 1 BATTERYMAINTENANCE 8 1 1 Notestoreplaceandinstallthebatteries 8 2...

Страница 4: ...sonnel exclusively Although we have made every effort to guarantee a com plete and accurate information in this user s manual we are not responsible for any errors or omissions that may exist The imag...

Страница 5: ...er s manual allows the end user to make any operating of both installation and commissioning in an easy and ordered way without doubt Finally once the equipment is commissioned and in operation it is...

Страница 6: ...ADVERTENCIA SLC TWIN PRO2 4 20 kVA This is a category C3 UPS product This is a product for commercial and industrial application in the second environment installation re strictions or additional mea...

Страница 7: ...ent will always prevail In the nameplate of the equipment the most important parameters and features can be checked Proceed with the installation accordingly StandardandB1 from4to10kVA Singlephaseinpu...

Страница 8: ...rent sharing signal under the cover Smart Slot Bat connector cover Battery connector StandardandB1 from8to10kVA Threephaseinputandsinglephaseoutput Digital input output RS232 USB EPO Manual bypass scr...

Страница 9: ...protection Battery module size 1 with 3x20 batteries and 50 A protection Battery fuses Terminal cover IEC inlet for AC power supply Terminal cover Battery switch Protection breaker Battery module siz...

Страница 10: ...10 SALICRU Battery switch Terminal cover Battery module size 2 with 4x20 batteries and 100 A protection Fig 3 Rear view of the battery module...

Страница 11: ...ording to Salicru s code 3 Quantity of batteries in one string 2x Quantity of strings in parallel Omitted for only one 0 Battery module with no batteries but with the needed accessories to fit them in...

Страница 12: ...to the worst conditions of input mains Wide input voltage range frequency range and wave shape so it is avoided the excessive use of the battery which has limited energy Available battery charger up...

Страница 13: ...r which is ac cepted by the main manufacturers of software and hardware The connection of the UPS with the SNMP is internal mean while the connection between the SNMP and the IT network is done by mea...

Страница 14: ...otect it against pos sible mechanical impacts dust dirt etc The equipment packaging has wooden pallet cardboard or wooden enclosure depending on the requirements ex panded polystyrene corners plastic...

Страница 15: ...e distances as the same UPS enclosure It is recommended to leave 75 cm additional free in each side for the possible tasks of the T S S or the needed power cable length to facilitate the movement of t...

Страница 16: ...hes which are only available in some models or equipments with extended back up times Ignore those operations related with your unit in case it does not have them Regarding the installation instructio...

Страница 17: ...lectrical regulations of the destination country The switches RCD and circuit breaker of a three phase input equipment connected to an IT power distribution system must break the NEUTRAL apart from th...

Страница 18: ...f the stated one in the UPS namopete 3 Relay for power contactor power supply 2 with 400V AC coil and NO contact type of 5A 1A minimum For parallel systems each equipment must have its own Backfeed pr...

Страница 19: ...mportant to pay attention to the following consideration Bonding PE stud U output phase Output neutral Main PE stud Input neutral R phase input Bonding PE stud U phase output 1 Output neutral 1 U phas...

Страница 20: ...lso the battery modules have protection and in this case they are doubled Once are internal by means of fuses and not ac cessible by the end user and the second ones by means of a two poles circuit br...

Страница 21: ...lly closed NC so it will open the electrical circuit when pressing it By means of the communication software the inverse func tion can be set Less particular cases it is better to not use this type of...

Страница 22: ...ructure N means the minimum quantity of equipments that the total load needs X means the quantity of redundant equipments that is to say the quantity of faulty UPSs that the system can allow at the sa...

Страница 23: ...both ports RS232 and USB at the same time Tab 4 shows the pin out of the RS232 signal in the DB9 female connector The RS232 is a serial data port so an important amount of information can be sent thro...

Страница 24: ...the risk of a long power outage for the first operating hours must be evaluated because the back up time of the UPS will be lower Do not start up the equipment and loads before section 6 states it Ne...

Страница 25: ...After a few seconds the UPS will be on Battery mode so it has to be considered their charge level the remaining back up time and the risk that means to operate on this operating mode If the AC mains i...

Страница 26: ...allel system again 6 4 PARALLEL SYSTEM OPERATING To operate with parallel systems in order to avoid prob lems check that the output 2 of each UPS is set to the same parameter in all of them The operat...

Страница 27: ...ear panel to On Turn the input circuit breaker switches from each UPS to On Turn the internal manual bypass switch of each UPS to UPS position The output switches of each UPS from switchgear panel mus...

Страница 28: ...erating mode as Frequency Converter With this operating mode the static bypass is disabled Tab 5 Control panel keypad functions The UPS has a control panel which has the following parts Four buttons w...

Страница 29: ...onnected at the output in by means of four segments which are equivalent to the following proportion 0 25 26 50 51 75 and 76 100 Information of the programmable outputs P1 It indicates that the progra...

Страница 30: ...e R R Phase R S S Phase S T T Phase T Tab 9 Abbreviations shown in the LCD 7 4 SETTINGS IN THE LCD CONTROL PANEL Parameter 1 Parameter 2 Parameter 3 Fig 28 Parameter layout in the LCD panel Parameter...

Страница 31: ...MOD BAT setting YES Output voltage setting SI 18 Battery capacity and quantity of strings setting SI 19 Back up time setting SI Tab 10 Code list for parameter 1 Description and setting depending on th...

Страница 32: ...Code 04 TWIN PRO2 TWIN 3 PRO2 Bypass frequency range Fig 33 Parameter 2 setting Minimum limit of the acceptable input frequency range When the nominal frequency is 50 Hz the setting range is from 46 t...

Страница 33: ...fting Bypass shifting is understood as that one that the end users make it over the own UPS I e when pressing the OFF key at the front of the equipment when it is on normal mode then the load is shift...

Страница 34: ...11 2 to 13 6 V If the battery voltage is lower than the entered figure the program mable output will be shutdown The preset factory figure is 11 2 V Code 12 TWIN PRO2 Hot standby function enable dis...

Страница 35: ...e is from 0 to 9 9 V and the preset factory figure is 0 V Code 15 TWIN 3 PRO2 Inverter voltage setting Fig 49 Parameter 2 setting Select Add or Sub to set the inverter voltage Parameter 3 setting The...

Страница 36: ...Parameter 2 setting It allows setting the battery capacity Parameter 3 setting It allows setting the MOD BAT quantity Code 19 TWIN 3 PRO2 Back up time setting Fig 54 Parameter 3 setting It allows sett...

Страница 37: ...e inverter on or when shutdown it The UPS does not supply output voltage The acoustic alarm beeps every two minutes TWIN 3 TWIN AC mode Description If the input voltage is inside the range the UPS wil...

Страница 38: ...me which will depend on their capacity also the acoustic alarm beeps every 4 sec TWIN 3 TWIN Bypass mode Description When the input voltage is inside the preset range and the bypass is enabled when th...

Страница 39: ...n error or fault the inverter will be blocked And the fault code will be displayed in the LCD panel and the icon will light Table 13 shows the error or fault codes and their description TWIN 3 TWIN Ta...

Страница 40: ...rvoltage 03 DC bus undervoltage 04 Unbalanced DC bus 06 Converter overcurrent 11 Inverter soft start fault 12 High inverter voltage 13 Low inverter voltage 14 Inverter output short circuited 1A Negati...

Страница 41: ...layed in the LCD panel Try to solve the problems by following the steps described in table 15 If the problem persists consult with our Technical Ser vice and Support T S S When necessary contact with...

Страница 42: ...rature is very high Check the fans and contact with the distributor Tab 15 Troubleshooting guide 8 3 WARRANTY CONDITIONS 8 3 1 Warranty terms The warranty conditions for this product can be found in o...

Страница 43: ...1 Voltage THD with linear load 1 2 Voltage THD with non linear load 4 5 Frequency With mains synchronised with nominal input 46 54 56 64 Hz Freerunning batterymode50 60 0 1Hz Freerunning batterymode50...

Страница 44: ...ticamente se trata de la uni n f sica entre la entrada de un dispositivo el ctrico con su salida DC La corriente continua CC en espa ol en ingl s DC de Direct Current es el flujo continuo de electrone...

Страница 45: ...in terrumpir la corriente el ctrica de un circuito cuando sta sobrepasa ciertos valores m ximos Modo On Line En referencia a un equipo se dice que est en l nea cuando est conectado al sistema se en c...

Страница 46: ...46 SALICRU...

Страница 47: ...47 SLC TWIN PRO2 UNINTERRUPTIBLE POWER SUPPLY UPS USER S MANUAL...

Страница 48: ...any salicru salicru_SA Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers The Technical Serv...

Отзывы: