31
Code
Decription
Bypass
mode/ No
output
mode
AC mode
ECO
mode
FC mode
Battery
mode
Battery
test
TWIN PRO2
TWIN/3 PRO2
01
Output voltage.
YES
-
-
-
-
-
02
Output frequency.
YES
-
-
-
-
-
03
Bypass voltage range.
YES
-
-
-
-
-
04
Bypass frequency range.
YES
-
-
-
-
-
05
Enable / disable ECO mode.
YES
-
-
-
-
-
06
ECO mode voltage range.
YES
-
-
-
-
-
07
ECO mode frequency range.
YES
-
-
-
-
-
08
Bypass mode setting.
YES
YES
-
-
-
-
09
Maximum battery discharge time setting.-
YES
YES
YES
YES
YES
YES
10
Reserved.
--
Reserved for future options.
-
Programmable output setting.
YES
YES
YES
YES
YES
YES
11
Reserved.
-
Reserved for future options.
-
Programmable level shutdown.
YES
YES
YES
YES
YES
YES
12
External MOD BAT setting.
-
YES
YES
YES
YES
YES
YES
-
Reservedo /Neutral lost.
YES
YES
YES
YES
YES
YES
13
Battery voltage setting.
YES
YES
YES
YES
YES
YES
14
Charger voltage setting.
YES
YES
YES
YES
YES
YES
15
Inverter voltage setting.
-
-
YES
-
YES
YES
-
16
Output voltage setting.
-
YES
-
YES
YES
-
17
External MOD BAT setting.
-
YES
-
-
-
-
-
-
Output voltage setting
SI
18
-
Battery capacity and quantity of strings
setting.
SI
19
Back up time setting.
SI
Tab. 10.
Code list for parameter 1. Description and setting
depending on the operating mode.
7.4.1. Setting menu views, depending on the parameter 1
code.
•
Code 01 (TWIN PRO2, TWIN/3 PRO2)
. Output voltage.
Fig. 29.
Parameter 3 setting: Output voltage.
It is possible to select one of the following output voltage
figures, phase to neutral value:
–
208, 220, 230 or 240 V.
•
Code 02
(TWIN PRO2, TWIN/3 PRO2)
. Output frequency.
Fig. 30.
Parameter 2 setting: Output frequency.
It is possible to select one of the following figures:
–
50 Hz, 60 Hz or ATO.
When ATO is selected, the output frequency is automatic
set to the frequency input detection, when the equipment
is supplied from mains.
If the frequency is between 46 and 54 Hz, the output
frequency will be set to 50 Hz and if it is between 56
and 64 Hz, it will be set to 60 Hz. The preset parameter
from factory is ATO.
Parameter 3 setting: Frequency mode.
Output frequency setting on FC mode or no FC mode. Two
SLC TWIN PRO2
UNINTERRUPTIBLE POWER SUPPLY (UPS)
USER'S MANUAL