7. CONTROL PANEL WITH LCD.
7.1. CONTROL PANEL.
Fig. 26.
Control panel view.
Button
Description
/ o
«
ON / ENTER
»
ON. Press this key for more than 0.5 sec. to start up the UPS
[inverter of the equipment].
ENTER. Press this key to confirm a selection in the setting
menu.
o
«
OFF / ESC
»
OFF. Press this key for more than 0.5 sec. to shutdown the
equipment, when the equipment is started up previously.
ESC. Press this key to escape and go back to the previous
setting menu.
/
o
«
TEST / UP
»
TEST. Press this key for more than 0.5 sec. to make a battery
test when the equipment works on AC or FC
(*)
UP. Press this key to show the next setting menu screen .
/
o
«
MUTE / DOWN
»
ALARM SILENT. Press it for more than 0.5 sec. to silent the
acoustic alarm (see section 6.2.3.2).
DOWN. Press this key to show the previous setting menu
screen.
/
o
«
TEST / UP
»
+
/
o
«
MUTE / DOWN
»
UP + DOWN. Press boht keys simultaneously for more than 1
sec. to enter and escape from setting menu .
(*) CF.
Operating mode as Frequency Converter. With this operating
mode the static bypass is disabled.
Tab. 5.
Control panel keypad functions.
•
The UPS has a control panel, which has the following parts:
Four buttons with the functions described in table 5.
A backlight LCD with the messages displayed as text or
graphics form, with black letter and blue backgrounds.
Four led indicators, which provides the following in-
formation:
–
Bypass
(yellow)
.
–
Line
(green)
.
–
Battery
(yellow)
.
–
Fault
(red)
.
Table 6 shows the individual function of each one of
them or their interaction with others, as regards to the
UPS status.
7.2. LED FUNCTIONS.
UPS status
Leds
Bypass
Line
Battery
Fault
UPS ON
No output mode
Bypass mode
AC mode
Battery mode
FC mode
ECO mode
Battery test
Fault
: Led permanent lighting.
: Led off.
Tab. 6.
Led optical indicators function.
7.2.1. Acoustic alarms.
Description
Modulation or alarme tone
Silent
UPS status
Bypass mode
Beep every 2 minutes.
Yes
Battery mode
Beep every 4 seconds.
Fault
Continuous.
Warning
Overload
2 Beeps every second.
Yes
Other
Beep every 1 second.
Faults
All
Continuous.
Yes
Tab. 7.
Acoustic alarms. Condition and modulation or
tone.