PDM20 Series
- 30 -
Function
code
Description
Set range
Unit Default Display
level
Modifi
cation
level
Notes
P1.10
Feedback
broken line
detection
value
0
~
1.00
V
0.10
When running
frequency reaches
MAX. running
frequency, after PID
feedback broken line
detection time (5s by
default), if PID
feedback value is still
smaller than PID
feedback broken line
detection value, it will
report feedback broken
line fault
P1.11
Feedback
broken line
detection
time
0
~
3600.0
s
5.0
The function is invalid
when it is set as 0
P1.12
Motor rated
power
0.2
~
4.0
kW
Set by
model
●
Set according to motor
nameplate
P1.13
Motor rated
frequency
10
~
60.00
Hz
Set by
model
●
Set according to motor
nameplate
P1.14
Motor rated
speed
0
~
36000
rpm
Set by
model
●
Set according to motor
nameplate
P1.15
Motor
ratedvoltag
e
0
~
480
V
220
●
Set according to motor
nameplate
P1.16
Motor rated
current
0.1
~
400.0
A
Set by
model
●
Set according to motor
nameplate
P1.17
User
password
0000
~
9999
1
○
P1.18
Function
choices of
M1
terminal
0
~
25
1
1
●
0
:
No function
1
:
Run
2
~
6
:
Reserved
Содержание PDM20 series