![SAJ PDM20 series Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/saj/pdm20-series/pdm20-series_user-manual_3523664030.webp)
PDM20 Series
- 29 -
Function
code
Description
Set range
Unit Default Display
level
Modifi
cation
level
Notes
P1.03
Sensor
range
0.1
~
500.0
bar
10
○
Same as P0.03
P1.04
Sensor
feedback
type
0
:
Voltage
feedback
1
:
Current
feedback
1
○
Same as P0.04
P1.05
power
setting of
sensor
0.0
~
25.0
V
25.0
○
Same as P0.05
P1.06
Upper limit
of running
frequency
P1.07
~
60.00
Hz
50.00
○
P1.07
Lower limit
of running
frequency
0.0
~
P1.06
Hz
0.00
○
P1.08
Action
choices
when
running
frequency
is lower
than lower
limit
frequency
0
~
2
2
○
0
:
Run at lower limit
frequency
1
:
Stop
2
:
Standby
P1.09
Carrier
frequency
setting
1.0
~
15.0 kHz
Set by
model
○
The value can be
adjusted properly to
adjust motor noise
Содержание PDM20 series