8000m Series
-
40
-
Function
Code
Function
Descriptions
Minimum
Unit
Factory
Setting
Modifica-
tion Type
F9.15
Lower frequency
of PID sleep
detecting
0.00Hz~20.00Hz
0.01Hz 10.00Hz
○
F9.16
~
F9.18
Reserved
FA Group: Protection and Malfunction Parameters
FA.00
Motor overload
protection
0:Disabled
1:Normal motor with low
speed compensation
2:Variable frequency
motor without low speed
compensation
2
●
FA.01
Motor over load
protection
20.0%~120.0% (motor
rated current)
0.1%
100.0%
○
FA.02
Threshold of
trip-free
70.0%~110.0% (standard
bus voltage)
0.1%
80.0%
○
FA.03
Decrease rate of
trip-free
0.00Hz~F0.10
0.01Hz
0.00Hz
○
FA.04
Over-voltage
stall protection
0:Disabled
1:Enabled
0
○
FA.05
Over-voltage
stall protection
point
110~150%
1%
120%
○
FA.06
Auto current
limiting level
50~200%
1%
160%
○
FA.07
Frequency
decrease rate
when current
limiting
0.00~50.00Hz/s
0.01Hz/
s
10.00Hz/s
○