8000m Series
-
22
-
Function
Code
Function
Descriptions
Minimum
Unit
Factory
Setting
Modifica-
tion Type
F0.11
Upper limit
frequency
source selection
0:Keypad setting (F0.12)
1:AVI terminal
2: Reserved
3: Multi-step speed
terminals
4: Communication
interface
0
○
F0.12
Upper limit
frequency
F0.14~ F0.10
0.01Hz 50.00Hz
○
F0.13
Reserved
F0.14
Lower limit
frequency
0.00Hz~ Upper limit
frequency F0.12
0.01Hz
0.00Hz
○
F0.15
The function
of lower limit
frequency
0: Running at lower limit
frequency
1: Stop frequency point
2: Sleep frequency point
0
○
F0.16
Carrier
frequency
setting
1.0~15.0kHz
1kHz
According
to model
○
F0.17
PWM mode
selection
0:PWM mode 1
1:PWM mode 2
2:PWM mode 3
0
●
F0.18
Acceleration
time 1
0.1~3600.0s
0.1s
According
to model
○
F0.19
Deceleration
time 1
0.1~3600.0s
0.1s
According
to model
○