17
• if parameter A0 is set to 0 or if parameter P4 is set to 1 andparameter A0 is set to 2, the device
records the alarms, oncondition that the instrument has stored no alarm of thistype or on
condition that the critical value is more criticalthan the one the instrument has stored
• if parameter u1 is set to 4, the alarm output will be acti
vated
Pr1
Cabinet probe error
Remedies:
• look at parameter P0
• check the integrity of the probe
• check the connection instrument-probe
• check the cabinet temperature
Effects:
• the compressor activity will depend on parameters C4 and C5
• defrosting will never be activated
• if parameter u1 is set to 4, the alarm output will be activated
• if parameter u1 is set to 5 or 6, the fourth output will be deactivated
Pr2
Evaporator probe error
Remedies:
• look at parameter P0
• check the integrity of the probe
• check the connection instrument-probe
• check the cabinet temperature
Effects:
• if parameter P3 has value 1, the defrost will last the timeyou will have set with parameter d3
• if parameter P3 has value 1 and parameter d8 has value 2,the instrument will work as if
parameter d8 had value 0
• if parameter F0 has value 3 or 4, the instrument will workas if the parameter had value 2
• if parameter u1 is set to 4, the alarm output will be activated
When the cause that has provoked the alarm disappears, the instru-ment restores the normal operation.
HACCP ALARMS
The device is capable of storing up to 2 HACCP alarms.
The device can furnish the following information:
• the critical value
• the alarm duration (from 1 minute to 99 hours and 59 minutes,partial if the alarm is ongoing).
CODE
ALARM TYPE (AND CRITICAL VALUE)
AL
minimum temperature alarm (the minimum temperatureof the cabinet or the minimum
temperature detected bythe auxiliary probe during an any alarm state of this type)
AH
maximum temperature alarm (the maximum temperatureof the cabinet or the maximum
temperature detected bythe auxiliary probe during an any alarm state of this type)
Warnings:
• the device records minimum temperature alarms andmaximum temperature alarms providing the
temperatureassociated with the alarm is the cabinet temperature(parameters A0 and A3 = 0) or the
temperature measuredby the auxiliary probe, providing its function is that ofdisplay probe (parameter P4 = 1
and parameters A0 = 2and A3 = 1)
• the instrument updates the information on the alarmson condition that the critical value is more critical
thanthe one the instrument has stored or on condition thatthe information has already been displayed
• no alarms will be recorded if the device is in stand-bymode.
When the cause of the alarm is resolved, the display returns to normal.
The HACCP LED provides information relating to the status of the HACCP alarm memory.
Viewing HACCP alarm information
To access the procedure:
• nsure the keyboard is not blocked and that no procedures arerunning
• press
for 2 s: the display will show the first available label
• press
or
to select “LS”
• press
he display will show one of the codes (AL, AH).
Содержание HD70
Страница 50: ......
Страница 74: ......
Страница 98: ......
Страница 122: ......
Страница 147: ...1 2 2 2 3 3 4 4 5 6 6 6 14 14 15 15 19 20 20 20 21 21 22 1 2 22 23...
Страница 148: ...2 1 2 4 5 9 10 HFC 7 11 12 1 2 3 4 5 6 B C D E F G H L R W...
Страница 149: ...3 13 14 15 OFF 16 17 18 19 20 21 22 23 24 25 26 27 28 29 48 30 31...
Страница 150: ...4 10 60 24 C C 0 4 9 0 4 9 0 4 9 0 2 0 4 0 3 10 0 4 8 0 2 8 0 2 8 0 2 8 0 3 8 23 24 18 18 20 18 0 4 32...
Страница 151: ...5 33 30 34 35 36 37 38 50 2 39 40 41 42 43 SHUKO N60320 44 30 45 46...
Страница 152: ...6 1 2 48 49 49a 50 N 51 1 2 2 48 15 15 SP r1 r2 C F 1 0 4 PA 15 19 15 4 SP 15 15 1 2...
Страница 161: ...15 0 10 6 20 61 22 15 6 5 6 48 C P2 F P2 Pr1 P0 49...
Страница 162: ...16 C0 C1 C2 C4 d7 dP F5 E0 0 C5 e C6 E1 0 F7 3 4 F4 F5 d3 E2 AH A0 A1b e A2b AL A0 A1A e A2A E2 E0...
Страница 165: ...19 LS AL AH AH HACCP 8 8 C 8 F dur h01 1 n15 1 15 AH 1 P5 60 LS HACCP 2 rLS 15 149 15 4 LED HACCP rLS 1 63 65 38...
Страница 166: ...20 66 67 74 68 71 OFF 16 17 62 73 30 OFF 16 17 76 77 78...
Страница 167: ...21 2002 96 EC 2002 96 WEEE...
Страница 168: ...22 WEEE 2002 96 12 82 F D D 12 1 2 82a F B E G B E D B E G D A B E G A 12...
Страница 170: ...24 1 29 2 30 3 31 6 44 8 44A 9 44B 9A 56 9B 69 10 75 10A 76 12 85 19 90 20 91 20A 96 21 101 22 102 25 113 4 28 113A 4...
Страница 171: ...2 1 46 4 7 12 13 15 14 11 10 5 set 16 17 18 Z Z Y 9...
Страница 172: ...19 20 21 22 23 24 25 26 27 28 29 30 set 31 32 75 83 64 150 83 64 204 204...
Страница 173: ...33 35 36 34 37 38 39 40 41 42 43 44 45 46 48 1 2 49 set 1 2...
Страница 174: ...50 51 set set set set set set set 52 53 54 60 1 61 20 MIN 1 63 65 2 73 71 66 67 69 68 74 ALCOOL 49a 1 2...
Страница 175: ...82 1 2 E 2 1 B A A D B E D E B A D F 76 77 78 82a 3 C C G G E 2 G D E B 3 D B 1 B A 3 D B 1 B A 2 2 F...