8
If you have to gain access the second level:
•
gain access the first level
•
press or
for selecting
•
press and
or
for setting
“-19”
.
•
press or
for 4 sec; the instrument will show
If you have to quit the procedure:
press
and
for 4 sec or do not operate for about 60 sec.
First level parameters
LABEL MIN. MAX U.M. DEF. PASSWORD
PA -55
99
- -19
password
LABEL MIN. MAX U.M. DEF. MEASURE
INPUTS
/1A
-10
10
°C/°F (6)
-1
cabinet probe calibration
/1b
-10
10
°C/°F (6)
0
evaporator probe calibration (it is important /Ab=1)
LABEL MIN. MAX U.M. DEF. REGULATOR
r0 0.1
15
°C/°F
(6)
3 hysteresis
(differential, it relative to the working setpoint)
Second level parameters
LABEL MIN. MAX U.M. DEF. MEASURE
INPUTS
/0
1
4
-
3
kind of probe (1=PTC, 3=NTC)
/1A
-10
10
°C/°F (6)
-1
cabinet probe calibration
/1b
-10
10
°C/°F (6)
0
evaporator probe calibration (it is important /Ab=1)
/5
0
1
-
0
temperature resolution (it is important if /8 = 1; 0 = 1 degree, 1 = 0.1 degrees)
/8
0
1
-
1
temperature unit of measure (0=Fahreenheit degree, 1=Celsius degree)
/Ab 0 1 -
1 evaporator
probe
presence
(and its functions; 1 = YES) (8) (9)
LABEL MIN. MAX U.M. DEF. REGULATOR
r0 0.1
15
°C/°F
(6)
3 hysteresis
(differential, it relative to the working setpoint)
r1 -99
r2
°C/°F
(6)
-22
minimum
value
you can assign to the working setpoint
r2
r1
99
°C/°F (6)
-15
maximum value you can assign to the working setpoint
r5
0
1
-
0
working setpoint modification lock-out (1 = YES)
r9
0.1
15
°C/°F (6)
1
hysteresis (differential, it relative to rA)
rA -99
99
°C/°F
(6)
-7
temperature the evaporator valve will be activated (cabinet temperature); look
at ur as well
LABEL MIN. MAX U.M. DEF. COMPRESSOR
PROTECTION
C0 0
240
min
0
minimum delay between you turn the instrument ON and the first compressor
activation
C1
0
240
min
5
minimum delay between two compressor activation in succesion
C2
0
240
min
3
minimum delay between two compressor gets OFF and the following activation
C4
0
1
-
0
fixed delay since the compressor gets ON and OFF(1=YES, for 3 s)
C5
1
240
min
10
cycle time for the compressor activation during the cabinet probe alarm
C6
0
100
%
50
percentage of C5 the compressor is ON during the cabinet probe failure (10)
LABEL MIN. MAX U.M. DEF. DEFROST
d0
0
99
h
6
defrost interval (7) (0=the defrost will never automatically be activated)
d1
0
1
-
0
kind of defrost (0=electric defrost, 1=hot gas defrost)
d2
-99
99
°C/°F (6)
8
defrost end temperature (evaporator temperature, it is important /Ab=1)
d3
0
99
min
30
defrost maximum length (0=the defrost will never be activated)
d4
0
1
-
0
defrost activation every time you turn the instrument ON (1=YES) (7)
d5 0
99
min
0
delay between you turn the instrument ON and the defrost activation (it is
important d4 = 1)
d6 0 1 -
1
freeze of the temperature showed by the instrument during the defrost (1 =
YES) (11)
d7 0
15
min
3 dripping
time
d9 0 1 -
0
compressor protections cleaning at the moment of the defrost activation (it is
important if d1=1; 1=YES)
dP 0
99
- 0
minimum time the compressor must have been ON at the moment of the defrost
activation in order that the defrost can be activated (it is important if d1 = 1) (12)
LABEL MIN. MAX U.M. DEF. ALARMS
A0 0.1
15
°C/°F
(6)
2
hysteresis (differential, it is relative to A1 and A2, it is important if A1 and/or
A2
≠
0)
A1A
-99
99
°C/°F (6)
-2
lower temperature alarm threshold; look at A2A as well
A2A 0 2 -
1
kind of lower temperature alarm (0 = it will never be activated, 1 = lower temperature
alarm relative to the working setpoint, 2 = absolute lower temperature alarm)
Содержание HD70
Страница 50: ......
Страница 74: ......
Страница 98: ......
Страница 122: ......
Страница 147: ...1 2 2 2 3 3 4 4 5 6 6 6 14 14 15 15 19 20 20 20 21 21 22 1 2 22 23...
Страница 148: ...2 1 2 4 5 9 10 HFC 7 11 12 1 2 3 4 5 6 B C D E F G H L R W...
Страница 149: ...3 13 14 15 OFF 16 17 18 19 20 21 22 23 24 25 26 27 28 29 48 30 31...
Страница 150: ...4 10 60 24 C C 0 4 9 0 4 9 0 4 9 0 2 0 4 0 3 10 0 4 8 0 2 8 0 2 8 0 2 8 0 3 8 23 24 18 18 20 18 0 4 32...
Страница 151: ...5 33 30 34 35 36 37 38 50 2 39 40 41 42 43 SHUKO N60320 44 30 45 46...
Страница 152: ...6 1 2 48 49 49a 50 N 51 1 2 2 48 15 15 SP r1 r2 C F 1 0 4 PA 15 19 15 4 SP 15 15 1 2...
Страница 161: ...15 0 10 6 20 61 22 15 6 5 6 48 C P2 F P2 Pr1 P0 49...
Страница 162: ...16 C0 C1 C2 C4 d7 dP F5 E0 0 C5 e C6 E1 0 F7 3 4 F4 F5 d3 E2 AH A0 A1b e A2b AL A0 A1A e A2A E2 E0...
Страница 165: ...19 LS AL AH AH HACCP 8 8 C 8 F dur h01 1 n15 1 15 AH 1 P5 60 LS HACCP 2 rLS 15 149 15 4 LED HACCP rLS 1 63 65 38...
Страница 166: ...20 66 67 74 68 71 OFF 16 17 62 73 30 OFF 16 17 76 77 78...
Страница 167: ...21 2002 96 EC 2002 96 WEEE...
Страница 168: ...22 WEEE 2002 96 12 82 F D D 12 1 2 82a F B E G B E D B E G D A B E G A 12...
Страница 170: ...24 1 29 2 30 3 31 6 44 8 44A 9 44B 9A 56 9B 69 10 75 10A 76 12 85 19 90 20 91 20A 96 21 101 22 102 25 113 4 28 113A 4...
Страница 171: ...2 1 46 4 7 12 13 15 14 11 10 5 set 16 17 18 Z Z Y 9...
Страница 172: ...19 20 21 22 23 24 25 26 27 28 29 30 set 31 32 75 83 64 150 83 64 204 204...
Страница 173: ...33 35 36 34 37 38 39 40 41 42 43 44 45 46 48 1 2 49 set 1 2...
Страница 174: ...50 51 set set set set set set set 52 53 54 60 1 61 20 MIN 1 63 65 2 73 71 66 67 69 68 74 ALCOOL 49a 1 2...
Страница 175: ...82 1 2 E 2 1 B A A D B E D E B A D F 76 77 78 82a 3 C C G G E 2 G D E B 3 D B 1 B A 3 D B 1 B A 2 2 F...