Configuration
Page 36 of 62
ZDUE-LTE-PLUS-VII
7.3.2
Class 79 - General operating parameters
This class describes the general operating parameters of the ZDUE-LTE-
PLUS-VII. It is defined as an open class, i.e. longer data sets than defined
here are accepted. The non-specified values are ignored in the evaluation
by the device. When reading out the parameters, only the specified values
are output.
Length of the class 79 record: 124 bytes
Factory configuration:
The factory configuration
(def.)
of
class 79
is shown in
bold.
Class 79
Parameter
Offset Len
Values (ASCII)
Description
String length
EVU identification
0
2
‘01‘ .. ‘16‘
Def. : '
08
EVU identification
2
16
‘ ‘ .. '~',
(0x20..0x7E)
EVU identification of the
ZDUE-LTE-PLUS-VII in the register
data set
Def.: '
00000000
'
String length Device address
(IEC address)
18
2
‘01‘ .. ‘16‘
Def.: '
08
'
Device address ZDUE-LTE-
PLUS-VII
20
16 ('0' .. '9', 'a' .. 'z',
'A' .. 'Z')
Def.: '
99999999
'
String length Set password
36
2
‘00‘ .. ‘16‘
Def.: '
08
'
Set password
38
16
‘ ‘ .. '~' (20h ..
7Eh) without '(' ,
')'
Def.: '
00000000
'
Head end system password
active
54
1
‘
0
‘
No password protection
‘1‘
Password without recall
String length head end
system password
55
2
‘
00
‘ .. ‘16‘
Length of the head end system
password
Def.: '
03
Head end system password
57
16
‘ ‘ .. '~' (20h ..
7Eh)
Def.:
PW0
String length Communication
ID
73
2
‘01‘ .. ‘16‘
Def.: '
15
Communication ID
75
16
‘ ‘ .. '~' (20h ..
7Eh)
Def.: '
1KGL923390R0003
'
Data format for the meter
interface
91
1
‘
0
‘
7 data bits, even parity, 1 stop bit
‘1‘
8 data bits, no parity, 1 stop bit
‘2‘
8 data bits, even parity, 1 stop bit
Mode C monitoring
92
1
‘
0
‘
Meter switching external meters
according to IEC61107 to mode C
is monitored
‘1‘
Purely transparent data operation
with fixed baud rate according to
start baud rate.
Transfer timeout [seconds]
93
2
'10' to '99
10 to 99 seconds
Def.: '
99