VG5 Installation & Quick-Start Manual
85
G
roup C
T
uni
ng
Fu
nc
tion C6
Ca
rri
er
F
requen
cy
C6-01
Carrier Frequency
Upper Limit
(Carrier Freq Max)
0.4~
15.0**
0.1 kHz 15.0** When control mode is vector
control (A1-02=2, 3), the setting
range of C6-01 and C6-02 is
2.0 ~15.0.
** Setting range and factory
setting differ depending on
inverter capacity.
x B B B B
C6-02
Carrier Frequency
Lower Limit (Car-
rier Freq Min)
0.4~
15.0
0.1 kHz 15.0**
x
A
A
-
-
C6-03
Carrier Frequency
Proportional Gain
(Carrier Freq Gain)
00~99** 1 00**
x
A A -
-
Fu
nc
tion C7 Hun
tin
g
Pre
ven
tion
C7-01
Hunting Prevention
Selection
(Hunt Prev Select)
0, 1
1
1
0: Disabled
1: Enabled
x A A - -
C7-02
Hunting Prevention
Gain
(Hunt Prev Gain)
0.00~
2.50
0.01 1.00
—
x
A A -
-
G
roup C
T
uni
ng
Fun
cti
on C
8 Fa
ct
or
y T
uni
ng
C8-08
AFR Gain
(AFR Gain)
0.00~
10.00
0.01 1.00
—
x
-
- A -
C8-09
AFR Time Constant
(AFR Time)
0~2000 1
ms 50
—
x
-
-
A
-
C8-30
<1110>
Carrier
Frequency
Selection during
Auto-tuning
(Carrier in tune)
0~2 1 0
0: Carrier frequency is
2 kHz.
1: Carrier frequency depends
on C6-01.
2: Carrier frequency is
5 kHz. (185~300 kW: 2.5
kHz)
x - -
A A
Function
Parameter
No.
Name
(Digital Operator
Display)
Setting
Range
Setting
Unit
Factory
Setting
Remarks
(Digital Operator Display)
Change
during
Operation
o: Enabled
x: Disabled
Parameter Access Level
User
Setting
V/f
V/f
w/
PG
Open
Loop
Vector
Flux
Vector
Appendix
VG5 Parameters
Содержание CIMR-VG5
Страница 1: ...VG5 Series Revision F Installation Quick Start Manual General Purpose Flux Vector Inverter with AVC TM...
Страница 2: ...2 VG5 Installation Quick Start Manual This page intentionally left blank...
Страница 36: ...36 VG5 Installation Quick Start Manual This page intentionally left blank...
Страница 60: ...60 VSG5 Installation Quick Start Manual This page intentionally left blank...
Страница 113: ...VG5 Installation Quick Start Manual 113 This page intentionally left blank Appendix Notes...