VG5 Installation & Quick-Start Manual
Gro
up H T
er
m
in
al
F
unc
tion
Func
tio
n H5 Ser
ial
C
om Setup
MODBUS C
ommuni
ca
tion
H5-01
Station Address
(Serial Comm Adr)
0~20 1 1F
—
x A A A A
H5-02
Communication
Speed Selection
(Serial Baud Rate)
0~4
0
3
0 : (1200 Baud)
1 : (2400 Baud)
2 : (4800 Baud)
3 : (9600 Baud)
4 : (19200 Baud)
<1110>
x
A
A
A
A
H5-03
Communication
Parity Selection
(Serial Com Sel)
0, 1, 2
1
0
0 : (No Parity)
1 : (Even Parity)
2 : (Odd Parity)
x A A A A
H5-04
Stopping Method
After Communica-
tion Error
(Serial Fault Sel)
0~3 1 3
0: (Ramp to Stop)
1: (Coast to Stop)
2: (Fast - Stop)
3: (Alarm Only)
x A A A A
H5-05
Timeover Detection
(Serial Flt Dtct)
0, 1
1
1
0 : (Disabled)
1 : (Enabled)
x A A A A
Prot
ec
tion
Func
tion L1
Motor
O
ver
lo
ad
L1-01
Motor Protection
Selection
(MOL Fault Select )
0, 1
1
1
0: (Disabled)
1: (Coast to Stop)
x B B B B
L1-02
Motor Protection
Time Constant
(MOL Time Const)
0.1~5.0
min.
0.1 min.
1.0
When O2-09=1 [American
Spec] the setting range is
0.1~20min. The factory default
setting then becomes 8 min.
8 min. is the operation time
from a cold start.
x B B B B
Protec
tion
Fu
nc
tion
L2 Powe
r Los
s Ri
de T
hro
ugh
L2-01
Momentary Power
Loss Detection
(PwrL Selection)
0, 1, 2
1
0
0 : (Disabled)
1 : Power loss ride through
(PwrL RideThru t)
2 : (CPU Power Active)
x B B B B
L2--02
Momentary Power
Loss Ride Through
(PwrL Ridethru t)
0.0~2.0 0.1s 0.7**
** Factory setting differs
depending on inverter capacity
(02-04).
x B B B B
L2-03
Min. Baseblock
Time
(PwrL Baseblock t)
0.1~5.0 0.1s 0.5*
* Factory setting differs
depending on inverter capacity.
Lower limit of setting range is
changed from 0 to 0.1.
<1110>
x B B B B
L2-04
Voltage Recovery
Time
(PwrL V/F Ramp t)
0.0~5.0
0.1s
0.3*
* Factory setting differs
depending on inverter capacity
(02-04).
x
A
A
A
A
L2-05
Undervoltage
Detection Level
(PUV Det Level)
150~
210
1V 190*
*Voltage Class
200V class=190V Det level
400V class=190V x 2= 380V level
575V class=190x575/200=546 level
x A A A A
L2-06
KEB Deceleration
Rate
(KEB Frequency)
0.0~
100.0
0.1% 0.0
—
x
A A A A
Function
Parameter
No.
Name
(Digital Operator
Display)
Setting
Range
Setting
Unit
Factory
Setting
Remarks
(Digital Operator Display)
Change
during
Operation
o: Enabled
x: Disabled
Parameter Access Level
User
Setting
V/f
V/f
w/
PG
Open
Loop
Vector
Flux
Vector
Appendix
VG5 Parameters
Содержание CIMR-VG5
Страница 1: ...VG5 Series Revision F Installation Quick Start Manual General Purpose Flux Vector Inverter with AVC TM...
Страница 2: ...2 VG5 Installation Quick Start Manual This page intentionally left blank...
Страница 36: ...36 VG5 Installation Quick Start Manual This page intentionally left blank...
Страница 60: ...60 VSG5 Installation Quick Start Manual This page intentionally left blank...
Страница 113: ...VG5 Installation Quick Start Manual 113 This page intentionally left blank Appendix Notes...