82
VG5 Installation & Quick-Start Manual
Gr
oup C
Tu
ni
ng
Fu
nc
tion C1
Ac
ce
l / De
ce
l
C1-01
Acceleration Time 1
(Accel Time 1)
Depends
on
C1-10
0.00~
600.00
or
0.0
~
6000.0
Depends
on
C1-10
0.01s or
0.1s
10.0
—
o Q Q Q Q
C1-02
Deceleration Time 1
(Decel Time 1)
10.0
—
o Q Q Q Q
C1-03
Acceleration Time 2
(Accel Time 2)
10.0
—
o B B B B
C1-04
Deceleration Time 2
(Decel Time 2)
10.0
—
o B B B B
C1-05
Acceleration Time 3
(Accel Time 3)
10.0
—
x A A A A
C1-06
Deceleration Time 3
(Decel Time 3)
10.0
—
x A A A A
C1-07
Acceleration Time 4
(Accel Time 4)
10.0
—
x A A A A
C1-08
Deceleration Time 4
(Decel Time 4)
10.0
—
x A A A A
C1-09
Emergency Stop
Time
(Fast Stop Time)
10.0
—
x B B B B
C1-10
Accel/Decel Time
Set Unit
(Acc/Dec Units)
0.1 1 1
0: Set unit of accel/decel time is
0.01s. (0.01 Seconds)
1: Set unit of accel/decel time is
0.1s. (0.1 Seconds)
x A A A A
C1-11
Accel/Decel Time
Switching
Frequency
(Acc/Dec SW Freq)
0.0~
400.0
0.1Hz
0.0
—
x A A A A
Function
Parameter
No.
Name
(Digital Operator
Display)
Setting
Range
Setting
Unit
Factory
Setting
Remarks
(Digital Operator Display)
Change
during
Operation
o: Enabled
x: Disabled
Parameter Access Level
User
Setting
V/f
V/f
w/
PG
Open
Loop
Vector
Flux
Vector
Appendix
VG5 Parameters
Содержание CIMR-VG5
Страница 1: ...VG5 Series Revision F Installation Quick Start Manual General Purpose Flux Vector Inverter with AVC TM...
Страница 2: ...2 VG5 Installation Quick Start Manual This page intentionally left blank...
Страница 36: ...36 VG5 Installation Quick Start Manual This page intentionally left blank...
Страница 60: ...60 VSG5 Installation Quick Start Manual This page intentionally left blank...
Страница 113: ...VG5 Installation Quick Start Manual 113 This page intentionally left blank Appendix Notes...