VG5 Installation & Quick-Start Manual
101
Prote
cti
on
Func
tion L3
Stal
l Pr
ev
en
tio
n Fu
nc
tion
L3-01
Stall Prevention
During Acceleration
(StallP Accel Sel)
0, 1, 2
1
1
0: (Disabled)
1: (General Purpose)
2: (Intelligent)
x B B B -
L3-02
Stall Prevention
Level During Accel-
eration
(StallP Accel Lvl)
0~200 1% 150
—
x
B B B -
L3-03
Stall Prevention
Limit During Accel-
eration
(StallP CHP Lvl)
0~100 1% 50
—
x
A A A -
L3-04
Stall Prevention
During Deceleration
(StallP Decel Sel)
0, 1, 2, 3
1
1
0: (Disabled)
1: (General Purpose)
2: (Intelligent)
<1110>
can use setting 2 for
all control modes
A102=0,1,2,3
3: With braking resistor
(Stall prev w/R)
When in Vector w/PG A1-
02=3 setting 3 cannot be set
with braking resistor and
with stall prevention.
x B B B B
L3-05
Stall Prevention
Selection during
Running
(StallP Run Sel)
0, 1, 2
1
1
0: (Disabled)
1: (Decel Time 1) C1-02
2: (Decel Time 2) C1-04
x B B - -
L3-06
Stall Prevention
Level during
Running
(StallP Run Level)
30~200 1% 160
—
x
B
B
-
-
L3-07
Stall Prevention
Function P Gain
(StallP Gain)
0.10~
2.00
0.01 1.00
—
x
F F -
-
L3-08
Stall Prevention
Function Integral
Time
(StallP Intg Time)
10~250 1
ms 100
—
x
F
F
-
-
Function
Parameter
No.
Name
(Digital Operator
Display)
Setting
Range
Setting
Unit
Factory
Setting
Remarks
(Digital Operator Display)
Change
during
Operation
o: Enabled
x: Disabled
Parameter Access Level
User
Setting
V/f
V/f
w/
PG
Open
Loop
Vector
Flux
Vector
Appendix
VG5 Parameters
Содержание CIMR-VG5
Страница 1: ...VG5 Series Revision F Installation Quick Start Manual General Purpose Flux Vector Inverter with AVC TM...
Страница 2: ...2 VG5 Installation Quick Start Manual This page intentionally left blank...
Страница 36: ...36 VG5 Installation Quick Start Manual This page intentionally left blank...
Страница 60: ...60 VSG5 Installation Quick Start Manual This page intentionally left blank...
Страница 113: ...VG5 Installation Quick Start Manual 113 This page intentionally left blank Appendix Notes...