Parameter description
Specification of SN200G high-performance vector convertor
- 88 -
Annexed Table 1 Multi-section Instruction’s Function Description
More than four segments command terminal, it can be combined into 16 states. Each state
corresponds to the 16 16 instruction set values. Specifically as shown in Table 1:
K
4
K
3
K
2
K
1
Instruction set
Corresponding parameters
OFF
OFF
OFF
OFF
Multi segment instruction 0
PC-00
OFF
OFF
OFF
ON
Multi segment instruction 1
PC-01
OFF
OFF
ON
OFF
Multi segment instruction 2
PC-02
OFF
OFF
ON
ON
Multi segment instruction 3
PC-03
OFF
ON
OFF
OFF
Multi segment instruction 4
PC-04
OFF
ON
OFF
ON
Multi segment instruction 5
PC-05
OFF
ON
ON
OFF
Multi segment instruction 6
PC-06
OFF
ON
ON
ON
Multi segment instruction 7
PC-07
ON
OFF
OFF
OFF
Multi segment instruction 8
PC-08
ON
OFF
OFF
ON
Multi segment instruction 9
PC-09
ON
OFF
ON
OFF
Multi segment instruction 10
PC-10
ON
OFF
ON
ON
Multi segment instruction 11
PC-11
ON
ON
OFF
OFF
Multi segment instruction 12
PC-12
ON
ON
OFF
ON
Multi segment instruction 13
PC-13
ON
ON
ON
OFF
Multi segment instruction 14
PC-14
ON
ON
ON
ON
Multi segment instruction 15
PC-15
When the frequency source selection for the multispeed function code PC-00 ~ PC-15 of 100.0%,
corresponding to the maximum frequency P0-10. Multi-step instructions except as a multi-speed function,
but also can be used as PID given source, or as a voltage source VF separation control, etc., to meet the
needs of different between a given value in switching.
Annexed Table 2 Acceleration and deceleration time selection terminal functions
Terminal 2 Terminal 1
Acceleration or deceleration time selection
Corresponding
parameter
OFF
OFF
Acceleration time 1
P0-17
、
P0-18
OFF
ON
Acceleration time 1
P8-03
、
P8-04
ON
OFF
Acceleration time 3
P8-05
、
P8-06
ON
ON
Acceleration time 4
P8-07
、
P8-08
Annexed Table 3 Motor selection Terminal functions
Terminal 2 Terminal 1
Motor selection
Corresponding parameter set
OFF
OFF
Motor 1
P1, P2 Group
OFF
ON
Motor 2
A2 Group
P4-10
DI filtering time
Factory
default
0.010s
Setting
range
0.000s
~
1.000s
Setting DI status of the terminal software filter time. If you are using the occasion input terminal susceptible to
interference caused by malfunction of this parameter can be increased in order to enhance the anti-jamming capability.
While this increases filter time can cause slow response DI terminal.