Parameter description
Specification of SN200G high-performance vector convertor
- 106 -
P7-10
Product No.
Factory default
Setting range
Inverter product number
P7-11
Software version number
Factory default
Setting range
Control panel software version number.
P7-12
Load speed display decimal digits
Factory default
0
Setting range
0
0 decimal places
1
1 decimal places
2
2 decimal places
3
3 decimal places
Load speed setting for the decimal display. The following example illustrates the calculation of load speed:
If the load speed display coefficient 2.000 P7-06, P7-12 load speed to 2 decimal places (two decimal places), when the
inverter operating frequency 40.00Hz, the load speed: 40.00 * 2.000 = 80.00 (2 decimal places display)
If the drive is shut down, the load speed display setting frequency corresponding to the speed, that is, “to set the load speed.”
To set the frequency 50.00Hz, for example, the stop state load speed: 50.00 * 2.000 = 100.00 (two decimal display)
P7-13
Cumulative power-up time
Factory default
0h
Setting range
0h
~
65535h
Cumulative power-time display from the factory started the drive.
This time reaches the set power-up time (P8-17), the inverter multi-function digital output (24) outputs ON signal.
P7-14
The total power consumption
Factory default
-
Setting range
0 to 65535 KWh
So far show the total power consumption of the drive.
P8 Group--Auxiliary function
P8-00
Jog frequency
Factory default
2.00Hz
Setting range
0.00Hz ~ maximum frequency
P8-01
Jog acceleration time
Factory default
20.0s
Setting range
0.00s~6500.0s
P8-02
Jog Deceleration time
Factory default
20.0s
Setting range
0.00s~6500.0s
When you define the drive jog a given frequency and the deceleration time.
Jog running, start fixed direct start-up mode (P6-00 = 0), stop mode is fixed to decelerate stop (P6-10 = 0).
P8-03
Acceleration time 2
Factory default
20.0s
Setting range
0. 0s
~
6500.0s
P8-04
Deceleration time 2
Factory default
20.0s
Setting range
0. 0s
~
6500.0s