Specification of SN200G high-performance vector convertor
Parameter description
- 120 -
P9-37
The first fault drive status
The same with
P9-17
~
P9-24
P9-38
The first fault power-on time
P9-39
The first fault running time
P9-40
The first fault frequency
P9-41
The first fault current
P9-42
The first bus voltage failure
P9-43
Input terminal status at fault first
P9-44
The first fault output terminal
P9-47
Fault protection action selection 1
Factory default
00000
Setting range
Single digit
Motor overload (Err11)
0
Freewheel
1
Halt according to halt mode
2
Continue to run
Ten bit
Input phase (Err12) (same unit)
Hundred bit
Output Phase (Err13) (same unit)
Thousand bit
External fault (Err15) (same unit)
Ten thousand bit
Communication Abnormal (Err16) (same unit)
P9-48
Fault protection action selection 2
Factory default
00000
Setting range
Single digit
Encoder failure (Err20)
0
Freewheel
1
Switch to VF, press the stop mode
2
Switch to VF, continues to run
Ten bit
Abnormal function code reader (Err21)
0
Freewheel
1
Halt according to halt mode
Hundred bit
Retention
Thousand bit
Motor overheating (Err 25) (same with P9-47 unit)
Ten thousand bit
Running time arrival (Err26) (same with P9-47 unit)
P9-49
Fault protection action selection 3
Factory default
00000
Setting range
Single digit
User-defined fault 1 (Err27) (same with P9-47 unit)
Ten bit
User-defined fault 2 (Err28) (same with P9-47 unit)
Hundred bit
Power-on time is reached (Err29) (same with P9-47 unit)
Thousand bit
Carrying out (Err30)
0
Freewheel
1
Halt according to halt mode
2
Decelerated to 7% of the rated motor frequency continues
to run, can not afford to load automatically returns to the
set frequency operation
Ten thousand bit Runtime PID feedback loss (Err31) (same with P9-47 unit)