Specification of SN200G high-performance vector convertor
Functional parameter table
- 39 -
Chapter 5 Functional parameter table
PP-00 is set to be non-zero value, namely setting the parameter protection password. Under mode of
functional parameter amd user-modified parameter, the parameter menu can only be accessed after
entering correct password. To cancel the password, PP-00 needs to be set as 0.
Parameter menu under mode of user-modified parameter is not protected with password. P group and
A group are basic function parameters, U group is monitoring parameter. The symbols in functional table
are as follows:
“
☆
”: It indicates the set value of the parameter can be changed under halt and running status of
frequency convertor;
“
★
”: It indicates the set value of the parameter can not be changed under running status of frequency
convertor;
“●”: It indicates the value of this parameter is the actually measured value and can not be changed;
“*”: It indicates that the parameter is “factory default” and can only be set by the manufacturer, and
users are prohibited to operate;
Table of basic functional parameters
Code
Name
Setting range
Default Change
P0 basic function group
P0-00
G / P Display type
1: G Type (Constant torque load model)
2: P Type (Fan and pump load model)
Depend on
machine type
●
P0-01
1
st
motor control mode
0: No speed Sensor vector control (SVC)
1: Speed sensor vector control (FVC)
2: V / F control
0
★
P0-02
Command source selection
0: Operation panel CMD channel (LED off)
1: Terminal CMD channel (LED lights)
2: Cmd channel (LED flashes)
0
☆
P0-03
Main frequency source X
selection
0: Digital setting (Preset frequency P0-08,
UP / DOWN can be modified, memory after
power failure)
1: Digital setting (Preset frequency P0-08,
UP / DOWN can be modified, no memory
after power failure)
2: AI1
3: AI2
4: AI3
5: PULSE setting (DI5)
6: Multi-stage command
7: Simple PLC
8: PID
9: Communication given
0
★
P0-04
Auxiliary frequency source Y
selection
Same as P0-03 (Main frequency source X
selection)
0
★
P0-05
Auxiliary superimposed
frequency source Y range
selection
0 : Relative to the maximum frequency
1 : Relative to frequency source X
0
☆
P0-06
Auxiliary superimposed
frequency source Y range
selection
0%
~
150%
100%
☆
Code
Name
Setting range
Default Change