Engineering manual - SAB 193-233-283 S A-frame (including ATEX)
008831 en 2022.02
145/175
Parameter
Unit
Method
Sabroe oil
PAO 68
Sabroe oil
AP 68
Sabroe oil
A 100
Target
spec.
Max.
Min.
Target
spec.
Max.
Min.
Target
spec.
Max.
Min.
Viscosity @40°C
cSt
ASTM D 445
66
76
53
64
74
51
100
115
80
TAN*1)
mg KOH/g
ASTM D 664
0.03
0.2
-
0.01
0.02
-
0.05
0.02
-
SAN*2)
mg KOH/g
ASTM D 665
-
0
-
-
0
-
-
0
-
Water
ppm
Karl Fisher
-
100
-
-
100
-
-
100
-
Apperarance
-
-
report
report
report
Colour
-
ASTM D 1500
report
report
report
Pentane Insolubles
(Sum)
W%
MM 490
-
0.05
-
0.05
-
-
0.05
-
Oxidation
abs/cm
IR,1700-1720/
cm
-
5
-
-
5
-
-
5
-
Nitration
abs/cm
IR,1627-1637/
cm
-
5
-
-
5
-
-
5
-
Nitro Compounds
abs/cm
IR,1547-1557/
cm
-
0.5
-
-
0.5
-
-
0.5
-
Maximum values for metal content in the oil)
Lead
ppm
ICP
-
10
-
-
10
-
-
10
-
Copper
ppm
ICP
-
10
-
-
10
-
-
10
-
Silicium
ppm
ICP
-
25
-
-
25
-
-
25
-
Iron
ppm
ICP
-
100
-
-
100
-
-
100
-
Chromium
ppm
ICP
-
5
-
-
5
-
-
5
-
Aluminium
ppm
ICP
-
10
-
-
10
-
-
10
-
Tin
ppm
ICP
-
10
-
-
10
-
-
10
-
1) TAN (Total Acid Number) is only non-ammonia applications
2) SAN (Strong Acid Number) is only reported for non-ammonia applications
A report is compiled for every sample received. This report will describe:
•
whether the oil can still be used without taking any further action.
•
whether the oil can be used after it has been filtered through a very fine filter. If this is
necessary, the oil must be pumped directly from the compressor unit through a 3 mi-
cron filter and back to the unit. The system must be completely closed to prevent the oil
from being affected by moisture in the air.
•
whether the oil can no longer be used.
The report will always be sent to the address stated on the sample label included in the form
set. A copy will be sent to Johnson Controls Denmark so that we are in a position to advise
you, if required.
11.12
Charging compressor with lubricating oil
Caution!
Only charge oil when the unit pressure is below 6 bar!
Oil charging is carried out by means of a portable oil charging pump, see Fig. 86. Proceed as
follows:
1.
Connect the high-pressure hose, pos. 7, to the service valve, pos. 106, on the unit via
the non-return valve, pos. 12. Use the correct reduction nipple. See Fig. 87.
2.
Place the free end of the suction hose from the pump, pos. 1, together with the by-pass
hose, pos. 2, in the barrel.
3.
Open the ball valve, pos. 9, and service valve, pos. 106, and start the pump, pos. 5.
Содержание SAB 193 S
Страница 1: ...SAB 193 233 283 S A frame including ATEX Screw compressor units Engineering manual EN...
Страница 2: ......