Register Name
Register
Address
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
config_display_
value_13
282
0x011A
unit_modbus
[0x0]
unit
[0x0]
CAL
[0]
semantic_meaning
[0x00]
283
0x011B
VSA
[0]
VEU
[0]
DSSA
[0]
DSEU
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
config_display_
value_14
284
0x011C
unit_modbus
[0x0]
unit
[0x0]
CAL
[0]
semantic_meaning
[0x00]
285
0x011D
VSA
[0]
VEU
[0]
DSSA
[0]
DSEU
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
config_display_
value_15
286
0x011E
unit_modbus
[0x0]
unit
[0x0]
CAL
[0]
semantic_meaning
[0x00]
287
0x011F
VSA
[0]
VEU
[0]
DSSA
[0]
DSEU
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
These registers hold the configuration of the 16 display values.
!!!
For both, unit and unit_modbus the following values are possible:
0x0
0x1
0x2
0x3
0x4
0x5
0x6
0x7
0x8
0x9
0xA
0xB 0xC
no
unit
°C
°F
cfm
l/s
m³/h
Pa
inWC V
%
%RH
ppm °F dec.
Bits 0-11 of the higher address of each configuration register indicate the symbols that are displayed along
with the corresponding display value.
These two bits define if the value displayed is taken from a display_value register at address 64 to 79 (see
Table 11 on Page 22) or from a sensor_value register at address 48 to 56 (see Table 10 on Page 21).
The following states are valid:
0 – defines that the value is taken from a display_value register that has to be set via modbus.
1 – defines that the value is taken from a sensor_value (+ offset_value) register that is automatically
updated with the current sensor value.
VEU:
Visible for End User
VSA:
Visible for System Administrator
These two bits define if the display value is visible for the end user and/or the system administrator.
If set to ‘1’ the value will be visible.
!!!
on Page 40 for example configurations of display values or set points.
semantic_meaning:
is used to provide information about the semantic meaning and the source of
the value. For further information please see Table 29 on Page 38.
CAL:
if set to ‘1’ the corresponding offset_value can be edited in
CALIBRATION-mode (only capable if DSEU or DSSA is set to ‘1’)
unit:
defines a unit with which the corresponding display value appears on the
LCD
unit_modbus:
defines a unit that the corresponding display value register appeare on
Modbus
DSEU:
Display Source for End User
DSSA:
Diplay Source for System Administrator
Table 27: Display Value Configuration