3.
Modbus
3.1.
Introduction
The device operates as a Modbus slave in Modbus RTU mode. The default baudrate is set to 57600, the default
parity is set to ‘none’ and the default address is set to 1. The communication with a Modbus master device will
work with Modbus function code 0x03 (Read Holding Registers) and Modbus function code 0x06 (Preset Single
Register). Section 3.4 shows all available Modbus registers.
3.2.
Modbus Network
Figure 6 illustrates a typical Modbus network setup with a linear bus topology used to connect several slave
devices to a master device. The transmission line has to be terminated at both ends. At the master device this can
be done by connecting a termination resistor.
Each RYMASKON 200 is equipped with a built-in 120Ω termination resistor. Set the termination switch to OFF
except on the last device on the bus where the termination switch must be turned ON. Per default each device has
the Modbus address set to 1. Because each address can only be used once it has to be configured at the device
settings in administration-mode.
For further information please see Section 2.2.
Figure 6: Modbus Network