Page 11 of 55
2.2.
User Interface
2.2.1.
General Description
The user interface consists of the LCD for displaying any desired value and up to eight touch buttons which are
used to adjust set points and change settings. Additionally up to four external push-buttons can be connected to the
device.
Figure 3: Front View RYMASKON 200
Each button can be configured individually via a Modbus register for its function (see Table 23 on Page 31). The
following listing gives you an overview which functionality can be associated with the buttons.
UP DOWN
change set point or device setting in EDIT-mode
directly access a set point in DISPLAY-mode
ON OFF
no specific function, the button state can be requested to control lighting
OCCUPANCY
no specific function, the button state can be requested to set occupancy
state
MENU
short press <3s: cycle through display values, set points or device
settings
long press ~3s: switch between DISPLAY-mode and EDIT-mode
long press >6s: switch to CLEANING-mode