![S+S Regeltechnik Rymaskon 200-Modbus Series Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/s-s-regeltechnik/rymaskon-200-modbus-series/rymaskon-200-modbus-series_user-manual_3093030024.webp)
RYM
ASKON
®
200-Modbus
Modbus Slave
User Manual
© S+S REGELTECHNIK GMBH
| THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |
Page 24 of 55
Register Name
Register
Address
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
buzzer_direct_access_0
102
0x0066
BE
[0]
R
[0]
R
[0]
R
[0]
R
[0]
R
[0]
R
[0]
R
[0]
buzzer_duration
[0x00]
buzzer_direct_access_1
103
0x0067
buzzer_mode
[0x00]
buzzer_tone
[0x00]
These registers are used to provide direct access of the piezo buzzer primarily used to give acoustic
feedback for the touch buttons.
BE
: Buzzer Enable Bit (1 – enabled/ 0 – disabled)
buzzer_duration
: 0x00 infinite, 0x01 - 0xFF duration in seconds
buzzer_mode
: defines specific alarm sound patterns
mode:
description:
< 1s pattern >
0
continuous
1
alarm 1
2
alarm 2
3
alarm 3
4
alarm 4
5
alarm 5
6
alarm 6
7
alarm 7
8
alarm 8
buzzer_tone
: 0x00 - 100 Hz, 0xFF - 1375 Hz (step-width = 5 Hz)
Table 14: Buzzer Direct Access