G
KINASGARD
®
DBWF ⁄ LF ⁄ FTF
Rev. 2020 - V27
The in-ceiling sensor
KINASGARD
®
DBWF ⁄ LF ⁄ FTF
is used to detect persons within a distance of up to 10 meters and to measure luminous
intensity or brightness, relative humidity and temperature. It has been designed for installation in suspended ceilings.
The sensor detects
motion
over an aperture angle of 110° and a perimeter of 360°. The patented lens system with 20 individual lenses results in
only very small dark areas that are only a few centimetres wide even at a distance of 10 m, thereby reliably detecting small movements. If motion is
detected, the potential-free relay output is switched. The hold time of the output, measured from the moment of the last detected movement, can
be preset internally in the device via potentiometer within a range of 4 seconds to approx. 17 minutes.
For the
temperature and humidity
, an analogue output 0 - 10 V corresponding to 0...+50 °C or 0...100 % r. H. is available. Deviations due to the
mounting position and location can be compensated internally using one offset regulator respectively.
For
luminous intensity or brightness
of 0...1000 lux or 0...5000 lux (selectable via DIP switches), an analogue output 0 - 10 V is also available. It is
also possible to activate the motion output depending on brightness with the help of a jumper.
Fields of application for the DBWF ⁄ LF ⁄ FTF include residential room monitoring, automatic switching of lights, control technology, alarm technology,
and motion-dependent control of room functions, e. g. for lowering the temperature in unused rooms.
TECHNICAL DATA
Power supply:
24 V AC ⁄ DC (half-wave rectification, read the instructions!)
Power consumption:
< 3.6 VA at 24 V DC
Electrical connection:
0.14 - 1.5 mm², via terminal screws
Outputs:
0 -10 V or inverted 10 - 0 V
(selectable via DIP switches)
MOTION
Sensor:
infra-red motion sensor
Detection range:
perimeter 360°, aperture angle 90° ⁄ 110°,
reach approx. 10 m, circular,
at an installation height of approx. 3 m the sensor covers a detection radius (r) of approx. 3.4 m
Motion detection:
of persons and objects, necessary temperature difference between subject and surroundings ≥ 5 K
Output, motion sensor:
potential-free changeover contact, for switching safety extra-low voltage only, up to 1 A
After-running time:
adjustable from 4 s to 17 min
LIGHT INTENSITY
Sensor:
light sensor with diffusor
Measuring range, light sensor:
0...1000 lux / 0...5000 lux (selectable via DIP switches)
Output, light sensor:
0 - 10 V
Deviation, light sensor:
typically < ± 10 % of final value (referred to calibration reference source, approx. 5700 K)
Temperature drift:
< ± 5 % of final value ⁄ 10 K at +20 °C
HUMIDITY
Measuring range, humidity:
0...100 % r.H. (output corresponding to 0 - 10 V)
Operating range, humidity:
10...95 % r.H. (non-precipitating air)
Deviation, humidity:
typically
± 3 % r. H.
(20...80 %); at +20 °C, otherwise ± 5 % r. H.
Output, humidity:
0 -10 V
TEMPERATURE
Measuring range, temperature:
0...+50 °C (output corresponding to 0 - 10 V) other measuring ranges on request!
Operating range, temperature:
0...+50 °C
Deviation, temperature:
typically ± 0.8 K at +20 °C, under standard conditions
Output, temperature:
0 -10 V
Ambient temperature:
0...+50 °C
Storage temperature:
–20...+50 °C
Housing:
steel, white painted
Housing dimensions:
cover: Ø 96 mm, height of housing: 30 mm
Installation dimensions:
ceiling cutout:
Ø 80 mm
installation depth: < 45 mm (incl. connector system)
on-wall protrusion: > 13 mm (motion sensor)
> 20 mm (humidity sensor)
Sensor protection:
mounted inside ceiling installation housing
Protection class:
III (according to EN 60 730)
Protection type (housing):
IP 20
(according to EN 60 529)
Standards:
CE conformity, electromagnetic compatibility according to EN 61 326, EMC directive 2014 ⁄ 30 ⁄ EU
KINASGARD
®
DBWF ⁄ LF ⁄ FTF
In-ceiling motion, light, temperature and humidity sensor
Type ⁄ WG02
Detection, Measuring Range
Output
Item No.
DBWF-LF-FTF-W
1.
Pr Motion
yes ⁄ no (relay on ⁄ off)
Changeover contact
1401-6114-3100-000
2.
Light Intensity
0...1000 lux ⁄
0...5000 lux (DIP)
0 -10 V (linearised)
3.
Temperature
0 ... 50 °C
0 - 10 V
4.
Humidity
0...100 % r.H.
0 - 10 V
Outputs:
0 -10 V or inverted 10 - 0 V
(selectable via DIP switches)