background image

Installing the Ruskin Electronic Controller
Install the Electronic Controller on an adjacent 

structural wall, plenum, or ductwork that is isolated 

from excessive system vibration. Do not mount the 

Electronic Controller to the fan housing.
Mount the Electronic Controller in a protected area  

of an air handling unit or place the Electronic Controller 

with similar control panels within the structure.
Install and store the Electronic Controller indoors in a 

non-condensing environment.
Mount the Electronic Controller within 50 feet (15.24 M) 

of the router to prevent voltage drop or distortion 

between the Electronic Controller and the sensors. 

Shorter cable lengths are better.
Mount the Electronic Controller on a flat surface 

using these steps: 
(note: The electronic controller must be accessible 

while the fan is running.)
1.  Securely mount the Electronic Controller on a wall 

near the sensors, in a position where the display 

can be easily viewed and the wiring connections 

are accessible. Use four field-supplied fasteners 

to mount the enclosure in an appropriate location. 

Use fasteners suitable for the wall material.

2.  Remove the six screws that secure the cover of 

the Electronic Controller to access set-up menu 

buttons.

3.  Remove the appropriate conduit plugs on the top 

of the Electronic Controller for connection of the 

field wires to the circuit board terminal blocks (see 

Figure 9).

4.  Wire the supply power and outputs. See Wiring.

IMporTAnT: Avoid running this device’s wiring in  

the same conduit as AC power wiring or with wiring 

used to suppy highly inductive loads such as motors, 

contactors and relays.
Tests show that fluctuating, erratic and inaccurate 

signal levels are possible when AC power wiring 

is present in the same conduit as the signal lines. 

Mount the Electronic Controller and all wiring away 

from variable frequency drives (VFD’s) and broadcast 

antennas.

IMporTAnT: Mount the Electronic Controller within 

50 feet of the router. Avoid cable loops or coils. 

Shorter cable lengths are better.
IMporTAnT: Always connect CAT5e cables from the 

sensors to the router, then the router directly to the 

Electronic Controller. Damage to the Controller will 

result if sensors are plugged directly to the controller.
If replacement cables between the router and the 

Electronic Controller are needed, they must meet the 

following spec:

CAT5e cable specs, with simple pairing:

CAT5e solid plenum cable 
4-pair shielded, twisted pair cable 
Shielded connectors 
24 AWG solid bare copper conductor 
Meets or exceeds CAT5e spec 
Teflon insulated, plenum jacket 
CMP rated for use in any area used for air return, 
drop ceiling, airducts, and in public buildings 
Compliant with EIA/TIA standards by ETL 
CSA listed

note: Standard Ethernet cables and crossover  

cables cannot be used because they do not have  

the correct simple pairing for connecting the  

router and the Electronic Controller.
The shielded sensor cables are hard wired and can- 

not be replaced. If the connector on the sensor cable 

needs to be replaced use the following pin-outs.

Содержание EFAMS

Страница 1: ...ance Manual Model EFAMS Electronic Fan Inlet Air Temperature Measuring Station with Electronic Controller II EFAMS 818 Replaces II EFAMS 316 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT PRI...

Страница 2: ...e harmful interference in which case the user will be required to correct the interference at his her own expense Only a qualified service technician should install this system To avoid unsatisfactory...

Страница 3: ...0 FT 3 05 M COMMUNICATION CABLES between Router and Electronic Controller Shielded CAT5e with shielded RJ45 type connectors using simple pairing 10 FT 3 05 M Standard 20 FT 6 10 M Optional 30 FT 9 14...

Страница 4: ...ct the fan inlet opening to ensure no obstructions or irregularities interfere with installation of the sensors Install the two fan inlet sensors opposite one another within the fan inlet bell Place t...

Страница 5: ...size in Table A Secure the sensor cables to the back of the rods with multiple zip ties The cables must be carefully and securely attached so that they do not move when the fan is operating Sensors s...

Страница 6: ...and outputs See Wiring IMPORTANT Avoid running this device s wiring in the same conduit as AC power wiring or with wiring used to suppy highly inductive loads such as motors contactors and relays Test...

Страница 7: ...r applied as accidental arcing may damage the prod uct and will void the warranty Figure 7a Setup and Adjustment Figure 7b Setup and Adjustment ROUTER CONNECTIONS During Normal Operation LED s will il...

Страница 8: ...amaged cable or an improperly ter minated cable REQUIRED INITIAL STARTUP FIELD CALIBRATION The EFAMS product is designed to introduce the least amount of pressure drop and corresponding energy penalty...

Страница 9: ...y Increase the fan speed to the second op erating air flow point With air passing across the sensors at the middle speed adjust the transmitter display using the up and down buttons until the value di...

Страница 10: ...reen clears To scroll through each of the menu options press UP and DOWN on the Electronic Controller see Figure 7 RESET SETTINGS LCD ON OFF ERROR INDICATION TEST SIGNAL UNITS GAIN OFFSET ZERO CUTOFF...

Страница 11: ...y want to make note of them before you reset the Electronic Con troller The default values are denoted in Figures 11 through 21 with an asterisk Figure 11 ARE YOU SURE Figure 12 DISPLAY Figure 13 ERRO...

Страница 12: ...Use UP and DOWN to select SI or IU unit systems Select SI for FPM or CFM with temperature in degrees Fahrenheit Select UI for MPS or LPS with temperature in degrees Celsius Use UP and DOWN to scroll t...

Страница 13: ...put of the Electronic Controller and the test and balance report adjust the gain We recommend setting the gain to 1 and taking multiple readings to determine the difference To calculate the gain divid...

Страница 14: ...culation and is applied to the 4 to 20 mA output signal only Scale Velocity mA Output Signal This option allows the user to improve the resolution of the output signals by changing the start and end p...

Страница 15: ...ure Display on the Electronic Controller ON or OFF AUTO RESET ON AUTO RESET OFF TEMPERATURE ON TEMPERATURE OFF Figure 23 Temperature Display ON OFF Submenu Figure 22 Auto Reset ON OFF Submenu Figure 2...

Страница 16: ...MC SPR is static safe and nonflammable Troubleshooting 3900 Dr Greaves Rd Kansas City MO 64030 816 761 7476 FAX 816 765 8955 www ruskin com Technical Specifications EFAMS Thermal Dispersion Fan Inlet...

Отзывы: