During Normal Operation LEDs illuminate at the RJ45 connector 

on the Electronic Controller. The left (green) LED indicates that 

the Electronic Controller has properly identified the router. The 

right (orange-yellow) LED       illuminates each time the Electronic 

Controller communicates with the router. See Figure 7b. 

If the right (orange-yellow) LED does not blink, reset the Elec-

tronic Controller by cycling the power switch OFF and then ON. 

See Figure 7. 

Use UP and DOWN (see Figure 7) to scroll through each sensor’s 

velocity and temperature reading. Press ESC on the Electronic 

Controller to display the average velocity and temperature values.

If an error occurs with one of the sensors, an error indication 

displays on the LCD screen. The error is indicated on the LCD 

screen by the velocity unit in lowercase letters. 

rEpAIr InForMATIon 

If the EFAMS Thermal Dispersion Fan Inlet Measuring System 

fails to operate within its specifications, replace the unit. For a 

replacement EFAMS System, contact the nearest Ruskin repre-

sentative. 

MAInTEnAnCE 

Once a year, scroll through the velocity and temperature values 

using UP and DOWN (see Figure 7).  Clean the sensor nodes if 

readings vary from normal readings.

To clean the electronic sensors: 

1.  Remove cover from Electronic Controller and turn power 

switch off. Please make sure the sensor is allowed to cool before 

cleaning.

2.  Unplug the shielded Cat5e cable from the RJ45 connector on 

the end of the thermal dispersion sensor. 

3.  Spray the thermal dispersion sensor with a non-flammmable 

circuit board cleaner if necessary. Ensure that the sensor is facing 

downward during cleaning so any moisture encountered in the 

cleaning process will drain out of the sensor.

4.  Remove lint, dust, and other matter from the sensor. (Do 

not use high pressure air.) Care must be taken not to bend the 

thermistors while cleaning. The sensor should be centered in its 

opening after cleaning.

Annually inspect the thermal dispersion sensor in unfiltered out-

side air, return air, or exhaust air applications to ensure that the 

thermal dispersion sensors are free of excessive buildup of lint, 

dust, or other airborne particulate. 

SuperClean Defluxer by MicroCare (MC-SPR) (or equal) can 

be used to spray clean the thermistors. MicroCare MC-SPR is 

designed for cleaning electronics, rosins and plastics. MicroCare 

MC-SPR is static safe and nonflammable. 

TroUBlEShooTIng

3900 Dr. Greaves Rd.
Kansas City, MO 64030
(816) 761-7476
FAX (816) 765-8955
www.ruskin.com

®

TEChnICAl SpECIFICATIonS     

EFAMS Thermal Dispersion Fan Inlet Airflow Measuring System 

Velocity requirements 

Minimum 0 fpm (0 mps)

 

Maximum 10,000 fpm (50.8 mps)

Fan Degradation 

Minimal

Sensor Accuracy 

Airflow: ±2% of reading and ±0.15% repeatability

 

Temperature: ±0.10°F

 

24 VAC internally fused power supply

 

Velocity Output: 4 to 20 mA (Std.) or 2 to 10 VDC (requires 500-ohm resistor)

 

Temperature Output: 4 to 20 mA (Std.) or 2 to 10 VDC (requires 500-ohm resistor)

 

Fused outputs

Electronic Controller 

Included

power requirement 

Dedicated 24 V, 40 VA transformer

power Consumption 

1 router with 2 sensors: 20 VA, 1 router with 4 sensors: 25 VA, 

 

2 routers with 8 sensors: 40 VA

operating Conditions 

Sensor: -25 to 140°F (-32 to 60°C); 0-99% RH, non-condensing 

 

Controller: -20° F to 120° F (-29° C to 49° C); 0-99% RH, non-condensing

router Unit (one per 

One microprocessor based multiplexer circuit

Fan location)

 

Sensor/communications circuit

 

All circuits encapsulated in electronic potting compound

Approximate weight 

Controller: 2.9 lb (1.32 kg)

 

Router: 1 lb (0.45 kg)

 

Sensor: 0.5 lb (0.22 kg)

Measuring stations are tested at an AMCA Registered Laboratory using instrumentation and procedures in accordance with AMCA Standard  

No. 610-93, Airflow Station Performance.
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifica-

tions, consult the local Ruskin office. Ruskin shall not be liable for damages resulting from misapplication or misuse of its products. 

Contact Ruskin Air & Sound Control, Air Measuring Product Sales

3900 Dr. Greaves Road Grandview, MO 64030.

Telephone: 816-761-7476

www.ruskin.com

Copyright 2018 Ruskin Manufacturing

The information provided in this manual is believed to be complete and accurate. Ruskin Manufacturing is a manufacturer and supplier of 

equipment and, as such, is not responsible for the manner in which its equipment is used nor for infringement of rights of third parties resulting 

from such use. System design is the prerogative and responsibility of the system designer.

All rights reserved. The product detailed in this manual is protected by a U.S. patent. Illustrations and product descriptions pub-

lished are not binding in detail. In keeping with its policy of continuous improvement, ruskin reserves the right to change or modify 

designs or specifications of products without notice or obligation.

Содержание EFAMS

Страница 1: ...ance Manual Model EFAMS Electronic Fan Inlet Air Temperature Measuring Station with Electronic Controller II EFAMS 818 Replaces II EFAMS 316 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT PRI...

Страница 2: ...e harmful interference in which case the user will be required to correct the interference at his her own expense Only a qualified service technician should install this system To avoid unsatisfactory...

Страница 3: ...0 FT 3 05 M COMMUNICATION CABLES between Router and Electronic Controller Shielded CAT5e with shielded RJ45 type connectors using simple pairing 10 FT 3 05 M Standard 20 FT 6 10 M Optional 30 FT 9 14...

Страница 4: ...ct the fan inlet opening to ensure no obstructions or irregularities interfere with installation of the sensors Install the two fan inlet sensors opposite one another within the fan inlet bell Place t...

Страница 5: ...size in Table A Secure the sensor cables to the back of the rods with multiple zip ties The cables must be carefully and securely attached so that they do not move when the fan is operating Sensors s...

Страница 6: ...and outputs See Wiring IMPORTANT Avoid running this device s wiring in the same conduit as AC power wiring or with wiring used to suppy highly inductive loads such as motors contactors and relays Test...

Страница 7: ...r applied as accidental arcing may damage the prod uct and will void the warranty Figure 7a Setup and Adjustment Figure 7b Setup and Adjustment ROUTER CONNECTIONS During Normal Operation LED s will il...

Страница 8: ...amaged cable or an improperly ter minated cable REQUIRED INITIAL STARTUP FIELD CALIBRATION The EFAMS product is designed to introduce the least amount of pressure drop and corresponding energy penalty...

Страница 9: ...y Increase the fan speed to the second op erating air flow point With air passing across the sensors at the middle speed adjust the transmitter display using the up and down buttons until the value di...

Страница 10: ...reen clears To scroll through each of the menu options press UP and DOWN on the Electronic Controller see Figure 7 RESET SETTINGS LCD ON OFF ERROR INDICATION TEST SIGNAL UNITS GAIN OFFSET ZERO CUTOFF...

Страница 11: ...y want to make note of them before you reset the Electronic Con troller The default values are denoted in Figures 11 through 21 with an asterisk Figure 11 ARE YOU SURE Figure 12 DISPLAY Figure 13 ERRO...

Страница 12: ...Use UP and DOWN to select SI or IU unit systems Select SI for FPM or CFM with temperature in degrees Fahrenheit Select UI for MPS or LPS with temperature in degrees Celsius Use UP and DOWN to scroll t...

Страница 13: ...put of the Electronic Controller and the test and balance report adjust the gain We recommend setting the gain to 1 and taking multiple readings to determine the difference To calculate the gain divid...

Страница 14: ...culation and is applied to the 4 to 20 mA output signal only Scale Velocity mA Output Signal This option allows the user to improve the resolution of the output signals by changing the start and end p...

Страница 15: ...ure Display on the Electronic Controller ON or OFF AUTO RESET ON AUTO RESET OFF TEMPERATURE ON TEMPERATURE OFF Figure 23 Temperature Display ON OFF Submenu Figure 22 Auto Reset ON OFF Submenu Figure 2...