Locating the Fan Inlet Sensors on 
centrifugal Forward Curve Fans

Mounting the Inlet Sensors

Inspect the fan inlet opening to ensure no 

obstructions or irregularities interfere with installation 

of the sensors. Install the two fan inlet sensors 

opposite one another within the fan inlet bell. Place 

the sensor housing at or near the highest restriction 

point of the fan inlet as possible. Be careful to not 

bend or touch the thermistors while installing.
Sensors should be placed at the 12:00 o’clock and 

6:00 o’clock positions, directly opposite one another 

in a similar fashion for fans with the air exiting on the 

right or left of the housing. See Figure 1.  
Sensors should be placed at the 3:00 o’clock and 

9:00 o’clock positions, directly opposite one another 

for fans with the air exiting on the top or bottom of 

the fan housing. See Figure 2.
On dual inlet fans, install two sensor circuits within 

each fan inlet bell. Place the sensor at or near the 

highest restriction point of each inlet as possible.  

Use the supplied pan head, self-drilling fasteners
(included in parts bag) to fasten the fan inlet sensor 
to the inlet bell. Use nylon cable clamps (included in 
parts bag) to secure RJ45 cable to the inlet bell.
If the fan has a shallow inlet bell, use a box knife or
other utility knife to remove the Air Leaving Wedge,
leaving the primary sensor housing (containing the
sensor circuit) and the Air Entering Wedge. Use the
mounting hole on the Primary Sensor Housing if you
remove the Air Leaving Wedge.

Locating the Fan Inlet Sensors on Forward 

Curve Fans 

 

Inspect the fan inlet opening to ensure no 

obstructions or irregularities interfere with installation 

of the sensors.  Install the two fan inlet sensors 

opposite one another within the fan inlet bell. Place 

the sensor housing at or near the highest restriction 

point of the fan inlet as possible.  

 

Sensors should be placed at the 12:00 o'clock and 

6:00 o'clock positions, directly opposite one another 

in a similar fashion for fans with the air exiting on the 

right or left of the housing.  See 

Figure 1

.   

 

Sensors should be placed at the 3:00 o'clock and 

9:00 o'clock positions, directly opposite one another 

for fans with the air exiting on the top or bottom of the 

housing. See 

Figure 2.

 

 

On dual inlet fans, install two sensor circuits within 

each fan inlet bell. Place the sensor housing at or 

near the highest restriction point of each inlet as 

possible.   

 

 

 

 

Figure 1: Sensor Mounting 

 

 

 

Figure 2: Sensor Mounting 

 

Mounting the Fan Inlet Sensors 

 

Use the supplied pan head, self-drilling fasteners 

(included in parts bag) to fasten the fan inlet sensor to 

the inlet bell. 

If the fan has a shallow inlet bell, use a box knife or 

other utility knife to remove the Air Leaving Wedge, 

leaving the primary sensor housing (containing the 

sensor circuit) and the Air Entering Wedge. Use the 

mounting hole on the Primary Sensor Housing if you 

remove the Air Leaving Wedge. 

 

 

Figure 3: Fan Inlet Sensor 

 

Note: 

Ensure that the airflow arrow is pointed in the 

correct direction. 

 

 

 

Figure 4: Fan Inlet Sensor Dimensions, in. (mm) 

  

 

RUSKIN EFAMS Thermal Dispersion Airflow Measuring System Installation Instructions 

Figure 1: Sensor Mounting

Figure 2: Sensor Mounting

rUSKIn EFAMS ThErMAl DISpErSIon AIrFlow MEASUrIng SYSTEM InSTAllATIon InSTrUCTIonS

4

Locating the Fan Inlet Sensors on Forward 

Curve Fans 

 

Inspect the fan inlet opening to ensure no 

obstructions or irregularities interfere with installation 

of the sensors.  Install the two fan inlet sensors 

opposite one another within the fan inlet bell. Place 

the sensor housing at or near the highest restriction 

point of the fan inlet as possible.  

 

Sensors should be placed at the 12:00 o'clock and 

6:00 o'clock positions, directly opposite one another 

in a similar fashion for fans with the air exiting on the 

right or left of the housing.  See 

Figure 1

.   

 

Sensors should be placed at the 3:00 o'clock and 

9:00 o'clock positions, directly opposite one another 

for fans with the air exiting on the top or bottom of the 

housing. See 

Figure 2.

 

 

On dual inlet fans, install two sensor circuits within 

each fan inlet bell. Place the sensor housing at or 

near the highest restriction point of each inlet as 

possible.   

 

 

 

 

Figure 1: Sensor Mounting 

 

 

 

Figure 2: Sensor Mounting 

 

Mounting the Fan Inlet Sensors 

 

Use the supplied pan head, self-drilling fasteners 

(included in parts bag) to fasten the fan inlet sensor to 

the inlet bell. 

If the fan has a shallow inlet bell, use a box knife or 

other utility knife to remove the Air Leaving Wedge, 

leaving the primary sensor housing (containing the 

sensor circuit) and the Air Entering Wedge. Use the 

mounting hole on the Primary Sensor Housing if you 

remove the Air Leaving Wedge. 

 

 

Figure 3: Fan Inlet Sensor 

 

Note: 

Ensure that the airflow arrow is pointed in the 

correct direction. 

 

 

 

Figure 4: Fan Inlet Sensor Dimensions, in. (mm) 

  

 

RUSKIN EFAMS Thermal Dispersion Airflow Measuring System Installation Instructions 

Locating the Fan Inlet Sensors on Forward 

Curve Fans 

 

Inspect the fan inlet opening to ensure no 

obstructions or irregularities interfere with installation 

of the sensors.  Install the two fan inlet sensors 

opposite one another within the fan inlet bell. Place 

the sensor housing at or near the highest restriction 

point of the fan inlet as possible.  

 

Sensors should be placed at the 12:00 o'clock and 

6:00 o'clock positions, directly opposite one another 

in a similar fashion for fans with the air exiting on the 

right or left of the housing.  See 

Figure 1

.   

 

Sensors should be placed at the 3:00 o'clock and 

9:00 o'clock positions, directly opposite one another 

for fans with the air exiting on the top or bottom of the 

housing. See 

Figure 2.

 

 

On dual inlet fans, install two sensor circuits within 

each fan inlet bell. Place the sensor housing at or 

near the highest restriction point of each inlet as 

possible.   

 

 

 

 

Figure 1: Sensor Mounting 

 

 

 

Figure 2: Sensor Mounting 

 

Mounting the Fan Inlet Sensors 

 

Use the supplied pan head, self-drilling fasteners 

(included in parts bag) to fasten the fan inlet sensor to 

the inlet bell. 

If the fan has a shallow inlet bell, use a box knife or 

other utility knife to remove the Air Leaving Wedge, 

leaving the primary sensor housing (containing the 

sensor circuit) and the Air Entering Wedge. Use the 

mounting hole on the Primary Sensor Housing if you 

remove the Air Leaving Wedge. 

 

 

Figure 3: Fan Inlet Sensor 

 

Note: 

Ensure that the airflow arrow is pointed in the 

correct direction. 

 

 

 

Figure 4: Fan Inlet Sensor Dimensions, in. (mm) 

  

 

RUSKIN EFAMS Thermal Dispersion Airflow Measuring System Installation Instructions 

Figure 3: Fan Inlet Sensor

note: Ensure that the airflow arrow is pointed in the 
correct direction.

Figure 4: Fan Inlet Sensor Dimensions, in. (mm)

120

(3048)

1

3

/

8

 (35)

1 (25)

3

1

/

8

 (79)

1

/

2

 (13)

Airflow

primary

Sensor

housing

Air

leaving 

wedge

Air

Entering 

wedge

Ambient

Thermistor

heated

Thermistor

remove piece for shallow

inlet bell installations

Содержание EFAMS

Страница 1: ...ance Manual Model EFAMS Electronic Fan Inlet Air Temperature Measuring Station with Electronic Controller II EFAMS 818 Replaces II EFAMS 316 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT PRI...

Страница 2: ...e harmful interference in which case the user will be required to correct the interference at his her own expense Only a qualified service technician should install this system To avoid unsatisfactory...

Страница 3: ...0 FT 3 05 M COMMUNICATION CABLES between Router and Electronic Controller Shielded CAT5e with shielded RJ45 type connectors using simple pairing 10 FT 3 05 M Standard 20 FT 6 10 M Optional 30 FT 9 14...

Страница 4: ...ct the fan inlet opening to ensure no obstructions or irregularities interfere with installation of the sensors Install the two fan inlet sensors opposite one another within the fan inlet bell Place t...

Страница 5: ...size in Table A Secure the sensor cables to the back of the rods with multiple zip ties The cables must be carefully and securely attached so that they do not move when the fan is operating Sensors s...

Страница 6: ...and outputs See Wiring IMPORTANT Avoid running this device s wiring in the same conduit as AC power wiring or with wiring used to suppy highly inductive loads such as motors contactors and relays Test...

Страница 7: ...r applied as accidental arcing may damage the prod uct and will void the warranty Figure 7a Setup and Adjustment Figure 7b Setup and Adjustment ROUTER CONNECTIONS During Normal Operation LED s will il...

Страница 8: ...amaged cable or an improperly ter minated cable REQUIRED INITIAL STARTUP FIELD CALIBRATION The EFAMS product is designed to introduce the least amount of pressure drop and corresponding energy penalty...

Страница 9: ...y Increase the fan speed to the second op erating air flow point With air passing across the sensors at the middle speed adjust the transmitter display using the up and down buttons until the value di...

Страница 10: ...reen clears To scroll through each of the menu options press UP and DOWN on the Electronic Controller see Figure 7 RESET SETTINGS LCD ON OFF ERROR INDICATION TEST SIGNAL UNITS GAIN OFFSET ZERO CUTOFF...

Страница 11: ...y want to make note of them before you reset the Electronic Con troller The default values are denoted in Figures 11 through 21 with an asterisk Figure 11 ARE YOU SURE Figure 12 DISPLAY Figure 13 ERRO...

Страница 12: ...Use UP and DOWN to select SI or IU unit systems Select SI for FPM or CFM with temperature in degrees Fahrenheit Select UI for MPS or LPS with temperature in degrees Celsius Use UP and DOWN to scroll t...

Страница 13: ...put of the Electronic Controller and the test and balance report adjust the gain We recommend setting the gain to 1 and taking multiple readings to determine the difference To calculate the gain divid...

Страница 14: ...culation and is applied to the 4 to 20 mA output signal only Scale Velocity mA Output Signal This option allows the user to improve the resolution of the output signals by changing the start and end p...

Страница 15: ...ure Display on the Electronic Controller ON or OFF AUTO RESET ON AUTO RESET OFF TEMPERATURE ON TEMPERATURE OFF Figure 23 Temperature Display ON OFF Submenu Figure 22 Auto Reset ON OFF Submenu Figure 2...

Страница 16: ...MC SPR is static safe and nonflammable Troubleshooting 3900 Dr Greaves Rd Kansas City MO 64030 816 761 7476 FAX 816 765 8955 www ruskin com Technical Specifications EFAMS Thermal Dispersion Fan Inlet...

Отзывы: