rUSKIn EFAMS ThErMAl DISpErSIon AIrFlow MEASUrIng SYSTEM InSTAllATIon InSTrUCTIonS

7

wIrIng 

Whenever possible, use a dedicated transformer 

for each EFAMS System. If you use a dedicated 

transformer for multiple EFAMS Systems, ensure that 

the transformer is rated with sufficient capacity for 

the total load of the connected sensors and other 

devices.
Errors in the load calculations can lead to problems. 

Wiring multiple low-voltage devices from a common 

transformer can result in lower-than-expected voltage 

at the device and higher-than-expected current draw 

when devices are connected a great distance from 

the power source.
Transformers are not required to be isolated from 

other devices. Isolation is only required to prevent 

electrical fluctuations due to intermittent high loads 

from causing problems with electronic devices.
See Figure 7 for supply power and output connec-

tions.
Follow these steps to make wiring connections: 
1. Connect 24 VAC power to the Electronic  

  Controller with a minimum of 20 VA. 

  a.  Connect 24 VAC hot to 24H + terminal. 

  b.  Connect 24 VAC common to 24C - terminal. 

  c. Negative (-) terminal to be connected to earth

    ground.
2.  Connect 4 to 20 mA velocity and temperature 

  outputs from the Electronic Controller to a Building  

  Automation System (BAS). 
Wiring from the 4-20 mA outputs to the Building 

Automation System (BAS) should be shielded twisted 

pair of at least 22 AWG for all wire connections. 

Larger gage wire may be required for long runs. All 

wiring must comply with applicable codes.
Note: The Electronic Controller provides two 4-20 mA 

signals to the building automation system.  Do not 

loop power.
Ruskin recommends wiring the system without power 

applied as accidental arcing may damage the prod-

uct and will void the warranty.

Figure 7a: Setup and Adjustment

Figure 7b: Setup and Adjustment

roUTEr ConnECTIonS

During Normal Operation, LED’s will illuminate at the 

RJ45 connector on the Electronic Controller as follows: 

On the T1 Communication Cable the (green) LED il-

luminates to indicate that the Electronic Controller has 

properly identified the router. The (orange-yellow) LED 

blinks each time the Electronic Controller exchanges data 

with the router. The T2 Power cable provides power only 

to the router and only the green LED will illuminate.

output           output

power                               

SW2    SW3    SW4    SW5

1-4

5-8

9-12

13-16

T1  T2 

 

Finishing the Installation 

 

 

 

1. Connect a shielded CAT5e cable between the 

Communication Port RJ45 connector on the router 

(see 

Figure 7 and Figure 8

) to the Communication 

Port RJ45 connector on the Electronic Controller 

(see 

Figure 7 and Figure 8

) .

 

 

 

 

2. Connect a shielded CAT5e cable between the Power 

Port RJ45 connector on the router (see 

Figure 7 and 

Figure 8)

 to the Power Port RJ45 connector on the 

Electronic Controller (see 

Figure 7 and Figure 8).

 

 

3. Use nylon cable clamps (included in parts bag) to 

secure RJ45 cable between the sensors and the 

router, and between the router and the Electronic 

Controler. Space cable clamps on 6 in. (152 mm) 

centers. 

4. Move the Electronic Controller’s power switch (see 

Figure 9)

 to the ON position. 

5. Use the LCD Contrast Adjustment screw (see 

Figure 9)

 to adjust the LCD contrast as desired: 

• Turn the screw clockwise to increase contrast. 

• Turn the screw counterclockwise to decrease 

contrast. 

6. Use the Options Menu to configure the Electronic 

Controller for your application. See 

Setup and 

Adjustments 

for specific instructions. 

7. After configuring the Electronic Controller, replace 

the cover. 

 

 

RUSKIN EFAMS Thermal Dispersion Airflow Measuring System Installation Instructions 

power

port

Communication

port

not

Used

not

Used

lCD Screen

6

1

/

8

 (156)

3

1

/

8

 (80)

11

3

/

8

 (290)

Figure 7c: Electronic

Controller Dimensions, in. (mm)

Содержание EFAMS

Страница 1: ...ance Manual Model EFAMS Electronic Fan Inlet Air Temperature Measuring Station with Electronic Controller II EFAMS 818 Replaces II EFAMS 316 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT PRI...

Страница 2: ...e harmful interference in which case the user will be required to correct the interference at his her own expense Only a qualified service technician should install this system To avoid unsatisfactory...

Страница 3: ...0 FT 3 05 M COMMUNICATION CABLES between Router and Electronic Controller Shielded CAT5e with shielded RJ45 type connectors using simple pairing 10 FT 3 05 M Standard 20 FT 6 10 M Optional 30 FT 9 14...

Страница 4: ...ct the fan inlet opening to ensure no obstructions or irregularities interfere with installation of the sensors Install the two fan inlet sensors opposite one another within the fan inlet bell Place t...

Страница 5: ...size in Table A Secure the sensor cables to the back of the rods with multiple zip ties The cables must be carefully and securely attached so that they do not move when the fan is operating Sensors s...

Страница 6: ...and outputs See Wiring IMPORTANT Avoid running this device s wiring in the same conduit as AC power wiring or with wiring used to suppy highly inductive loads such as motors contactors and relays Test...

Страница 7: ...r applied as accidental arcing may damage the prod uct and will void the warranty Figure 7a Setup and Adjustment Figure 7b Setup and Adjustment ROUTER CONNECTIONS During Normal Operation LED s will il...

Страница 8: ...amaged cable or an improperly ter minated cable REQUIRED INITIAL STARTUP FIELD CALIBRATION The EFAMS product is designed to introduce the least amount of pressure drop and corresponding energy penalty...

Страница 9: ...y Increase the fan speed to the second op erating air flow point With air passing across the sensors at the middle speed adjust the transmitter display using the up and down buttons until the value di...

Страница 10: ...reen clears To scroll through each of the menu options press UP and DOWN on the Electronic Controller see Figure 7 RESET SETTINGS LCD ON OFF ERROR INDICATION TEST SIGNAL UNITS GAIN OFFSET ZERO CUTOFF...

Страница 11: ...y want to make note of them before you reset the Electronic Con troller The default values are denoted in Figures 11 through 21 with an asterisk Figure 11 ARE YOU SURE Figure 12 DISPLAY Figure 13 ERRO...

Страница 12: ...Use UP and DOWN to select SI or IU unit systems Select SI for FPM or CFM with temperature in degrees Fahrenheit Select UI for MPS or LPS with temperature in degrees Celsius Use UP and DOWN to scroll t...

Страница 13: ...put of the Electronic Controller and the test and balance report adjust the gain We recommend setting the gain to 1 and taking multiple readings to determine the difference To calculate the gain divid...

Страница 14: ...culation and is applied to the 4 to 20 mA output signal only Scale Velocity mA Output Signal This option allows the user to improve the resolution of the output signals by changing the start and end p...

Страница 15: ...ure Display on the Electronic Controller ON or OFF AUTO RESET ON AUTO RESET OFF TEMPERATURE ON TEMPERATURE OFF Figure 23 Temperature Display ON OFF Submenu Figure 22 Auto Reset ON OFF Submenu Figure 2...

Страница 16: ...MC SPR is static safe and nonflammable Troubleshooting 3900 Dr Greaves Rd Kansas City MO 64030 816 761 7476 FAX 816 765 8955 www ruskin com Technical Specifications EFAMS Thermal Dispersion Fan Inlet...

Отзывы: