13
Airflow-IQ Start-up & Commissioning Guide
Ruskin AMS Object List
AI – Analog Input
AO – Analog Output
AV – Analog Value
BI – Binary Input
BO – Binary Output
BV – Binary Value
MI – Multi-State Input
MO – Multi-State Output
MV – Multi-State Value
R – ReadOnly
W – Writable
C – Commandable (Contains Priority Array)
Example 1:
Example 2:
Example 3:
Name
Description
Type Inst Access Units
Def Details
RuskinAMS
Application Version
AI
1
R
no-units
-
AirflowSetpoint
Current Airflow Rate Setpoint
AI
2
cfm
-
Airflow
Current Airflow Rate
AI
3
R
cfm
-
AirVelocity
Current Air Velocity
AI
4
R
fpm
-
DamperPosition
Damper Position Feedback
AI
5
R
pct
-
DpReading
Differential Pressure Sensor Value
AI
6
R
inches-water
-
DamperArea
Damper Area
AV
1
W
square-feet
4
MaxControlAirflow Maximum Controllable Airflow Rate AV
2
W
cfm
5000
Ka
Damper Ka Factor
AV
3
W
no-units
2400
Factor1/m
Damper 1/m Factor
AV 4
W
no-units
0 .5
BACnetSetpoint
BACnet Control Setpoint
AO 1
C
percent
0
EnableStatus
Damper Enabled Status (Safety)
BI
1
R
percent
-
off=alarm
on=normal
DamperMode
Damper Mode
V
1
W
no-units
1
1=Flow;
2=Position;