Use probes conforming to IEC61557-5 when measuring current and voltage.
Open-circuit voltage Um: Max. About 50Vpp, rectangle wave.
Short-circuit current lm: Max.20mA, but Im
☓
(
RH +RE
)
< Um
Measuring frequency : 94Hz
、
105Hz
、
111Hz
、
128Hz, manual selection.
Measuring time: Typical 12 seconds.
Measuring error for RH, RS : typical (RH+RS+RE) 10%
Additional error for RH MAX or RS MAX: 3%+10
Series interference voltage: in 400 Hz
、
60 Hz
、
50 Hz
、
16
2
3
Hz system frequency or input series
interference voltage by DC voltage through E and S terminals. The mean square root value of r.m.s. in
series interference voltage is
3V. (DC is excluded in 20Ω range)
Additional error for 3V series interference voltage:5%+10.
After measuring the probe resistance, auxiliary earth resistance and earth resistance, the Instrument will
display a Warning notice to indicate over high RS or RH value if the measurement error is higher than
30% when considering impacting conditions.
Earth Resistivity (ρ)
Range
Measuring Range
Resolution
Accuracy
20Ω·m
0Ω·m
~
19.99Ω·m
0.01Ω·m
depends on RG
ρ
=
2×π×a×RG
200Ω·m
20.0Ω·m
~
199.9Ω·m
0.1Ω·m
2000Ω·m
200Ω·m
~
1999Ω·m
1Ω·m