exceeding the preset limit value which indicates over-high interference voltage, the measurement will be automatically
prohibited
When Ust
≥
20V, the testing result interface displays
“ ” warning, and prohibits measurement. When Ust
>
50V, the
testing result interface displays
“OL” as well.
Auxiliary earth resistance testing Function
Auxiliary earth resistance
(
Rh
、
Rs
)
value measurement and display function.
When Rh or Rs value exceeds
4kΩ+100
☓
RE or
50kΩ(no matter higher than anyone) , the Main Screen displays
or
or
warning message.
When Rh or Rs value exceeds 50
kΩ, the result
“
OL” displayed on the Main Screen.
These parameters are measured automatically at auxiliary earth resistance measurements, and can be recalled on
the Main Screen.
Note: Rh and Rs stand for Auxiliary Earth Pole H(C) and the Auxiliary Earth Resistance of S(P) respectively.
Connection of Earth Test Leads and Auxiliary Earth Spikes
Connect the Earth Test Leads to the connectors on the instrument firmly. Otherwise, a contact failure occurs may
result in measurement error. See individual measurement for detailed connection methods for reference.
(Make sure the auxiliary earth spike goes beyond the fall-of-potential range of earthed electrode and auxiliary earth
electrode. Leave 20m or more intervals between earth electrode, auxiliary earth electrode and auxiliary earth spikes can
satisfy the requirement.)
Section Five
Starting measurement
Danger
No voltage should be applied between the measuring terminals at earth resistance measurements!
Earth Resistance Measurement
Precise measurement (3 pole)