Generalization
The instrument is a multifunctional earth resistance/earth resistivity tester equipped with a microcomputer.
The instrument employs digital signal settlement technology, which can draw earth measurement signals, possess
features of high frequency, high accuracy and high resistance, and measure earth resistance/ earth resistivity accurately.
The instrument can execute standard 3POLE and 4POLE earth resistance measurements and has 2POLE earth
resistance measurement and earth resistivity calculation functions as well.
The Instrument conforms to the following Safety Requirements:
IEC61010-1
(
CAT
Ⅲ
600V,POLUTION degree
Ⅱ)
IEC61557-1
、
5
(
Electronic safety requirements for low voltage distribution system below AC 1000v and DC 1500v
)
Basic Measurement Function
2/3/4- pole earth resistance measurement
Earth resistivity
(
ρ
)
calculation
Earth Resistance Measurement employs AC simulation test, 4-kind of testing frequencies
(
94Hz
、
105Hz
、
111Hz
、
128Hz
)
,which are selectable by hand to reduce impacts from low interference sources.
Auxiliary Earth Resistance Measurement Function
Testing and displaying auxiliary earth resistance.
Warning Display Function for auxiliary earth resistance upper-limits
Displaying warnings for inaccurate measurements due to high auxiliary earth resistances
Auto-range Function in Resistance Measurement and OL displays for over range.
Indication Functions for high interference voltage.