background image

·

 

 

 

1) 

Connect the yellow green wire with the 

  label of the power cable to the PGND in the power strip in the 

equipment room. 

2) 

Connect the brown wire with the "+" label of the power cable to the -48 VGND in the power strip in the 

equipment room. 

3) 

Connect the blue wire with the "-" label of the power cable to the -48 VDC in the power strip in the equipment 

room. 

3. 

Install the plug of the DC power cable to the PD240I according to Figure b.

 

1) 

Insert the power plug into the PD240I. 

2) 

Check the wire color. The sequence should be yellow green, blue, and brown from left to right.   

3) 

Fasten the two screws on the power plug.   

A connection cable with brown, blue and yellow green wires is provided when the PD240I leaves the factory. On one 

end, there is a three-core plug. You can directly insert it into the PD240I and fasten it. On the other end, there are three 

wires with the "+", "-", and 

  labels respectively and are connected to the DC power supply systems in the 

equipment room.   

Check whether the power cables are correctly installed before you power the device on.   

 

Before installing the power module, ensure that the power switch is off.   

3.6.2  Removing the DC Power Module 

Note: This section applies to the removal of the RSR30-X routers. The module to be removed is the PD240I DC power 

module. 

Perform the following steps to remove power cables: 

1. 

Turn the power switch of the router to the OFF position. 

2. 

Loosen the screws on the plug and then pull the plug out of the PD240I according to Figure b in section 2.4.1. 

3. 

Remove the DC power cable from the DC terminal block in the chassis. 

 

Before removing the power module, ensure that the power switch is off.   

3.7  Installation Check 

When you have installed the router, before powering on it, do as follows: 

 

If the router is stalled in a cabinet, check the installation brackets of the cabinet and router are firm. If the router is 

stalled on the workbench, check there is enough room around the router for heat dissipation and the workbench is 

firm. 

 

Check the power supply meets the requirements. 

 

Check the grounding cable is correctly connected. 

 

Check the router is connected correctly to other devices like the configuration terminal. 

Содержание RSR30-X-SPU10

Страница 1: ...RSR30 X Series Router Hardware Installation and Reference Guide...

Страница 2: ...m or by any means without the prior written consent of Ruijie Networks is prohibited Exemption statement This document is provided as is The contents of this document are subject to change without any...

Страница 3: ...http community ruijienetworks com Technical Support Email service_rj ruijienetworks com Skype service_rj ruijienetworks com Related Documents Documents Description Configuration Guide Describes networ...

Страница 4: ...dustries such as telecommunications private network ISP finance tax public security and railways as well as middle and large sized enterprises The RSR30 X has the following features Reliability advanc...

Страница 5: ...rt both service modules and power supplies support hot swapping Power Redundancy Support Memory DDR 2 GB FLASH 512 MB I O Interface Ethernet interface Nine GE ports GE 0 0 0 0 0 8 that support auto ne...

Страница 6: ...or is not properly inserted or the module can be unplugged Blinking green The module is initializing Solid green Initialization is complete and the module is operational SD SD card status indicator O...

Страница 7: ...d either is available at a time The port for mini USB is the mini USB B connector and only the 5 pin mini B connector or compatible connector cable can be used To use the U Console port install the de...

Страница 8: ...ly when no SD card is inserted or no installation package is available on the SD cards If no installation package is available on the inserted SD card and USB flash disk the system resets and but does...

Страница 9: ...Figure 1 3 Appearance of Two M5000E AC60 Power Supply Modules Indicators Indicator Description Indicator on the panel Green Power output is normal Red Power output is abnormal Off There is NO power o...

Страница 10: ...ecifications of the M5000E AC60 Module Module Model RG PD240I Rated Voltage Range 36VDC 72VDC Power 60W Hot Swapping Supported Power Redundancy Supporting 1 1 power redundancy Overvoltage Protection 1...

Страница 11: ...e UPS to prevent power failure and other interferences 2 1 1 Electrical Safety Please observe local regulations and specifications when performing electrical operations Relevant operators must be qual...

Страница 12: ...perature and humidity in the equipment room If the humidity is high for a long time mechanical changes like faulty insulation or even electrical leakage may occur If the relative humidity is low the i...

Страница 13: ...d resist interference Please carefully check the grounding conditions on the installation site according to the grounding requirements and perform grounding properly as needed Safety Grounding The equ...

Страница 14: ...ng protection 2 2 8 Checking Installation Location Whether the router is installed in a cabinet or placed on a workbench make sure There is enough room at the inlet wind gap and the vent of the router...

Страница 15: ...PC with hyper terminal installed Router modules Power sockets Some tools are customer supplied 3 Router Installation 3 1 Procedure for Installing Router Please follow the following procedure to instal...

Страница 16: ...routers The module to be installed is the M5000E AC60 power module 1 Place the router in such a way that you face the rear panel of its host 2 Remove the empty barrier on the slot where the power mod...

Страница 17: ...he power supply socket should be installed near the device for convenient plugging 3 4 Installing the Grounding Cable and the Power Cable Ruijie RSR30 X series routers support the following AC power s...

Страница 18: ...ct one end of the supplied power cable to the socket on the rear panel of the cabinet and another to the AC power socket 2 Turn the router to power on position 3 Check the power indicator on the front...

Страница 19: ...terminal block in the chassis Figure 3 2 PD240I Power Plug Installation The installation procedures are as follows 1 Take the DC power module PD240I and cables from the carton and insert the DC power...

Страница 20: ...r cables are correctly installed before you power the device on Before installing the power module ensure that the power switch is off 3 6 2 Removing the DC Power Module Note This section applies to t...

Страница 21: ...the same port and either is available at a time The 4 pin mini B USB may be easily confused with the 5 pin mini B USB Only the 5 pin mini B connector can be used 4 Router Startup and Configuration 4 1...

Страница 22: ...at you may cut power supply in time in case of accident 4 1 2 2 Powering on Router Turn the router to the power on position 4 1 2 3 Check after Powering on After powering on the router please check If...

Страница 23: ...5 MTD_NAND_FOUND 1 NAND chips chip size 536870912 detectedCopyright c 1998 2014s by Ruijie Networks All Rights Reserved Neither Decompiling Nor Reverse Engineering Shall Be Allowed Jan 1 00 02 29 SYS...

Страница 24: ...er 4 during the start will appear on the terminal If a fault occurs nothing or illegible characters will appear If no information appears on the terminal display please check If the power system is wo...

Страница 25: ...pasted on the curved position or other positions that may affect the installation The text on a label must be in the format from left to right or from up to down as shown in Figure 6 1 Details are as...

Страница 26: ...the two ports connected by the cable Write the content based on the onsite environment 1 Write information about the local end in Area 1 2 Write information about the peer end in Area 2 3 Area 3 will...

Отзывы: