·
Hardware Installation and Reference Guide Appendix B: Cabling Recommendations
If cables are to be bent, bind them first but do not tie cable ties within the bend to avoid stress on the cables, which
may otherwise cause the wires inside to break, as shown in Figure B-3.
Figure B-3 Do Not Tie Cable Ties within the Bend
Wrap up unnecessary or excess cables and bind them to the appropriate rack position, where device operation is not
affected and no damages occur to the device and cables during debugging.
Do not bind power cords to the rails for moving parts.
Leave a certain length of the cable connecting moving parts, such as the ground wire of the cabinet door, to avoid
stress on the cable; When moving parts are in place, ensure the excess cable length shall not contact heat sources,
sharp corners or edges. If heat sources are unavoidable, use high-temperature cables instead.
When using screws to fasten cable lugs, the bolts or nuts shall be tightened and prevented from loosening, as shown
in Figure B-4.
Figure B-4 Fastening Cable Lugs