Rubicon Synapse H2O Скачать руководство пользователя страница 13

H2O Manual | 13

Error

Name

Description

Action

0

No Error

System normal

N/a

1

Display error

LED fault  

detedcted

Return for repair

2

PV over voltage

DC input voltage 

too high

Too many PV 

panels

3

PV leakage de-

tected

RCM has detected 

leakage current

Check for electrical 

faults

4

Water over temp

Oveer max  

tempreture de-

tected

Return for repair

5

No temp probe 

detected

Tempreture probe 

is not connected

Connect probe

6

Temp error

Implausible  

tempreture reading

Check probe  

installation

7

Safety cut out 

activated

Temp or RCM 

safety active

Check for faults

8

Termal cutout

Max tempreture 

limit 

Check system

9

Element fault

Element fault 

detected

Check element

10

Internal fault

Internal fault  

detected in H2O

Return for repair

Basic use cases (off-grid installation)

»

When  sufficient  solar  power  is  available

H2O will be on and can heat.

»

When  insufficient  solar  power  is  available

H2O will be off and will not heat.

6.3 Default settings

The H2O can work directly out of the box with 

no further settings or internet connection. 

The factory temperature settings are as follows 

and cannot be changed without connecting 

the H2O to the internet and the user app (see 

section 7):

AC setpoint

55°C 

Solar setpoint

55

°C 

Boost setpoint

55

°C 

Note:

 it is recommended that an internet 

connection is used and commissioned as it 

enables full diagnostics and configuration of the 

device. 

6.4 Led status indicators

The H2O uses the front panel LEDs to indicate 

its status. 4 Multicolour indicators are used and 

their colours designate the following possible 

statuses:

Temp LED Solar LED

Grid LED

Status LED 

(2 colour flash)

Heating

Solar heating Grid heating  Normal 

AP mode

At setpoint Grid mode

Solar mode

Normal

Wifi connected

Cooling

Solar off

Grid off

Error

AP mode

Error

Wifi connected

6.5 fault finding

If the H2O does not work correctly or displays 

a fault is present with the Status LED, it is 

necessary to correct an abnormal occurrence. 

All error status messages are available in the 

User App. Once an error is corrected, reset the 

fault by turning off / on both PV and AC together. 

The following table shows monitored faults 

which can occur and possible solutions:

6.6 Other errors

Besides the errors specifically listed above, the 

following errors may also occur: 

Fuses: 

The Synapse H2O has 2 fuses inside, 1 each 

for the AC and DC supplies. Should either 

supply fail to correctly power up the unit, check 

these 2 fuses on the main board. (See Figures 

6 and 7 below). 

Figure 8. AC Fuse

Figure 9. DC Fuse

Содержание Synapse H2O

Страница 1: ...Synapse H2O PV Geyser Controller Technical Manual www rubiconsa com...

Страница 2: ...0 General safety requirements 7 3 11 Local requirements 7 3 12 Other considerations 7 4 Device description 8 4 1 Overview and description 8 4 2 Identification 8 5 Installation 9 5 1 Safety 9 5 2 Insta...

Страница 3: ...Figure 1 below shows a typical installation 1 1 Contents of the box Inside the box you should find 1 x Synapse H2O controller 1 x mounting bracket 1 x securing screw 1 x temperature probe 1 x pair MC...

Страница 4: ...ximum Power Output 1500W MPPT Range 130 220VDC depends on element Connection MC4 Solar Connectors Installation Pre requisites External PV Isolator and SPD protection Voltage 60 220V Modulated DC varia...

Страница 5: ...d to IEC 60730 ICASA RF approval pending CE Self Certified for EMC Safety IEC 60950 1 Electrical Safety Designed to Class B IEC 60730 Maximum Ambient Temperature 0 C to 30 C full output limited output...

Страница 6: ...staff lies with the company that the staff work for It is also the responsibility of the company to assess the ability of the worker to carry out any kind of work and ensure their safety Staff must co...

Страница 7: ...10 general safety requirements Operator The person in charge of handling the electrical device is responsible for the safety of persons and property Avoid accidental re connection of the system using...

Страница 8: ...the LED indicators please see the Operation section of the manual For more detailed information on the LED indicators please see the Operation section of the manual Figure 2 H2O PV geyser controller R...

Страница 9: ...as free airflow and at least 300mm clearance all around Is not subjected to heat generated by another device eg above a cooker or directly adjacent to the geyser It may not be mounted inside a cupboar...

Страница 10: ...or the local isolator depending on local regulations Ensure that the Live Neutral and Earth conductors are all connected securely and according to the labels on the H2O and the Geyser Ensure that the...

Страница 11: ...ectors on the H2O See Fig 5 Ensure that the H2O is protected with Surge Protection Devices SPD s on both the AC and DC supply interfaces Temperature sensor The H2O is supplied with a temperature senso...

Страница 12: ...stem will remain below dangerous temperature levels To do this set the original mechanical thermostat marginally above the desired setpoints of the system but still within safe limits For example if t...

Страница 13: ...and the user app see section 7 AC setpoint 55 C Solar setpoint 55 C Boost setpoint 55 C Note it is recommended that an internet connection is used and commissioned as it enables full diagnostics and c...

Страница 14: ...py of which is available at www rubiconsa com H2O 7 Mobile applications and WiFi connectivity 7 1 APP introduction The Synapse H2O can be commissioned configured and monitored via the included Mobile...

Страница 15: ...ubiconsa com Once accredited an installer can enrol a site by opening the Installer s app with a mobile web browser from https rubicon installation web app login and logging in with the credentials yo...

Страница 16: ...eps have been completed tap the submit button Step 5 Finalise installation documentation This step gives the PDF summary document time to generate and download The installer must confirm the Installat...

Страница 17: ...main PCB for 3 seconds 7 4 User s App Synapse H2O is managed monitored and controlled with the H2O User s app The User s Application requires a Synapse H2O s user to have been enrolled by a Qualified...

Страница 18: ...s You can change the temperature setpoints for Grid Solar and Boost modes here Support Contact Rubicon for support from here Menu Energy consumption This view allows you to visualise your energy usage...

Страница 19: ...elow the Login button 7 4 1 Forgotten password If a user forgets or loses their password it can be reset Enter this link in a mobile device s browser https rubicon iot dev web app login In the screen...

Страница 20: ...sa com Port Elizabeth 4 Reith Street Sidwell Port Elizabeth Eastern Cape 6061 27 41 451 4359 salespe rubiconsa com East London Unit 1 Aloe Industrial Park Motor City Bonza Bay Road Beacon Bay East Lon...

Отзывы: