24. Alarm Card Address Settings
Dual Channel Alarm Card Address And Output Drive Type Settings
Before each card is placed within the annunciator a unique address No. has to be set using the
switches located on DIL switch SW1, which allows the programming module to communicate and
pass programming instructions to and from the associated alarm channels. When replacing an alarm
card the switches on DIL Switch SW1 must be set to match the card that is being removed.
SW1-*
FUNCTION
ON
OFF
SW1-1
Set address Bit 1
1
0
SW1-2
Set address Bit 2
1
0
SW1-3
Set address Bit 3
1
0
SW1-4
Set address Bit 4
1
0
SW1-5
Set address Bit 5
1
0
SW1-6
Set address Bit 6
1
0
SW1-7
Set address Bit 7
1
0
24.1 Set Output Drive To Operate With LED
SW1-8
Fit & forget LED assemblies
SW1-8
OFF
Alarm Card DIL Switch SW1 Location
SW1 DIL SWITCH
OFF
ON
OFF
ON
A45
06-
*
RL2
RL1
ALARM CARD
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8