24
SPR Card Showing Relay And Jumper Locations
CONTACT STATE
FUNCTION
REF.
RELAY
LINK
OPEN
CLOSED
Critical horn relay
HNA
RL1
LK1
N/O
N/C
Non critical horn relay
HNB
RL2
LK2
N/O
N/C
Critical group relay
GPA
RL3
LK3
N/O
N/C
Non-critical group relay
GPB
RL4
LK4
N/O
N/C
Multifunctional relay
MUL
RL5
LK5
N/O
N/C
Pt No CB4642POP1
N/C
RL2 - HNB
HORN RELAY
RL3
GPA
GROUP
RELAY
RL5
MULT.
FUNCT.
RELAY
LK5
RL4 - GPB
GROUP RELAY
N/O
LK4
N/O
N/C
N/C
N/O
LK3
1ST
COMM'S
STD
L
K
1
0
RBH
GP
WD
COMM'S
STD
CONTACT SET
NORMALLY CLOSED
NORMALLY OPEN
RL1
HNA
HORN
RELAY
LK6
LK2
LK8
LK7
LK9
N/O
LK1
N/C
N/O
N/C
N/O
N/C
7.2 Critical Horn Relay - HNA
When an alarm occurs the horn relay will change state and remain in the alarm condition until the
mute or ack pushbutton has been pressed. Each channel can be set to operate the critical horn relay
as required. Please note:- Channels set to operate the critical horn relay will also operate the integral
audible alarm.
7.3 Non-Critical Horn Relay - HNB
When an alarm occurs the relay will change state and remain in the alarm condition until the mute or
ack pushbutton has been pressed. Each channel can be set to operate the non- critical horn relay as
required. Please note:- Channels set to operate the non-critical horn relay will not operate the integral
audible alarm.