22. Function No Key And Descriptions
If units are supplied with unarmed alarm channels it is necessary to jump over these missing cards
(addresses) to access the next channel.
General Description
The P725 is equipped with numerous pre-defined features that can be simply enabled or disabled on
a per channel basis as required. Functions numbers are assigned to each feature for ease of
selection.
Feature and Function Key
FEATURE
FUNCTION
STATUS LED
OFF
ON
Monitor current input contact state
FO
Alarm Contact
Open
Alarm contact
closed
Set signal contact non alarm state
F1
Normally
Open
Normally
closed
Set individual channel repeat
Relay non alarm state
F2
Normally
energised
Normally
de-energised
Set automatic or manual
Reset function
F3
Manual
Reset
Automatic
reset
Set fleeting alarm state
F4
Lock in
Non lock in
Set alarm to ringback sequence
F5
N/A
Ringback
Pushbutton interlock
F6
Enable
Disable
Input reflash
F7
Disable
Enable
Reflash critical group relay
F8
Disable
Enable
Reflash non critical group relay
F9
Disable
Enable
Set alarm to first up sequence F0
F10*
Disable
Enable
Set alarm to first up sequence F1
F11
Disable
Enable
Set alarm to first up sequence F2
F12
Disable
Enable
Set alarm to first up sequence F3
F13
Disable
Enable
Set alarm to be in first up group A
F14*
Disable
Enable
Set alarm to be in first up group B
F15
Disable
Enable
Set alarm to be in first up group C
F16
Disable
Enable
Set alarm to be in first up group D
F17
Disable
Enable
Set repeat relays to follow logic
F18
Disable
Enable
Set repeat relays to follow input
F19
Disable
Enable
Set repeat relays to follow lamps
F18 & F19
Disable
Enable
Repeat relays inhibited on test
F20
Disable
Enable
Set alarm to critical group relay
F21*
Disable
Enable
Set alarm to non critical group relay
F22*
Disable
Enable
Set alarm to critical horn relay
F23*
Disable
Enable
Set alarm to non critical horn relay
F24*
Disable
Enable
Note 1:- The Functions marked with the * are the default settings if no programming is requested with
the order
Note 2:- Functions F2, F18 & F19 are only available if individual channel repeat relays are fitted
(Option RLY).