38
Relays RL5 - RL8:-
RL5 - RL8 are factory supplied as normally energised relays and any relay can be
software configured to one of the following functions
Group Relay 1 – 6
Any channel configured to the associated group will de-energise the relay on alarm
and the relay will remain in the abnormal state until the alarm has been cleared and re-
set
Group Relay 1 - 6 with reflash function added
Additional HA or HB Horn relay
Combined HA & HB Horn relay
Internal fault
Printer fault
Log fault
GPS fault
Sync. fault
Reflash Common Alarm Relays
Group relays can be software configured to allow the associated relay contacts to drop
out and re-alarm, reflash, if additional alarms occur in the same group whilst the Relay
is already in the alarm state.