SECTION 4 – OPERATING INSTRUCTIONS
Pre-checks
The system is supplied fully tested and, if requested, pre-configured to suit your
application so detailed on site re-testing should not be necessary.
After connections have been completed the following pre-checks should be made
before applying power.
1. Ensure the equipment is earthed using the specific earth stud on the right-hand
side of the P925TS-RK Euro-rack.
2. Check that the power supply is adequately rated and suitable for the primary
supply available and that the output voltage is suitable for use with the 9000TS
system.
3. The 9000TS System requires a 24VDC logic supply and the 24VDC signal
supply is derived from this supply as standard. (Options exists for high voltage
inputs fed via external power source as detailed within this manual)
4. Check that all cards are fully seated and the retaining screws have been
tightened.
5. Check all alarm contacts are volt-free and correctly wired using the common
v24VDC available on teVC for standard systems (Options
exists for high voltage inputs fed via external power source as detailed within
this manual)
6. Care should be taken with the output wiring to the display to ensure no shorts
occur.
7. Please note a short in the output will not damage the equipment but could give
extremely misleading results.
Status LED
Each card is supplied with a status LED which is used for fault and setup indication as
follows:-
LED STATUS
ON Normal
Operation
OFF
Faulty card or card not recognised in software
Power ON
After completing the above pre-checks, power can be supplied to the unit. The system
will complete an initial self-test and will search for all of the installed cards. During this
time the status LED on the associated input / output card will illuminate as soon as the
system recognises the card and its settings.