System 9000TS
85
Address 254 will contain contact data for inputs 255.
Address 255 will contain contact data for inputs 256.
Etc.
Bespoked systems supplied before August 2011 may have additional data types
available, please contact RTK for specific information / manual.
After August 2011 all systems have the data types, contact offset and port offset
functionality defined below:-
There are two data groups containing data types these are listed below together with
their default address range. Contact and port offsets are assumed to be 0:-
Status Group – Data types
o
Contact,
Address range 0 – 1984 max.
o
Alarm,
Address
range 2000 – 3984 max.
o
Relay,
Address
range 4000 – 5984 max.
o
Disable, A
ddress
range 6000 – 7984 max.
o
Inhibit, A
ddress
range 8000 – 9984 max.
o
Shelved, A
ddress
range 10000 – 11984 max.
o
Internal, A
ddress
range 12000 – 13984 max.
o
Channel Fault, A
ddress
range 14000 – 15984 max.
Port Group – Data types
o
Coil,
Address range 16000 – 17984 max.
The data type returned depends on the combination of Start address, Contact Offset,
Port Offset and number of inputs.
Note: If status and coil first data bits overlap “coincide” the data type returned will
always be Status.
Status data type -
Address of first data bit = Start address - Contact Offset.
Examples below with Contact offset = 0:-
Default – Start address 0 - Contact status data for input 1.
Default – Start address 2000 - Alarm status data for input 1.
Default – Start address 4000 - Relay Contact status data for input 1.
Default – Start address 6000 - Disable status data for input 1.
Default – Start address 8000 - Inhibit Contact status data for input 1.
Default – Start address 10000 - Shelved status data for input 1.
Default – Start address 12000 - Internal status data for input 1.
Default – Start address 14000 – Channel Fault status data for input 1.
Examples below with Contact offset = 40000:-
Default – Start address 40000 - Contact status data for input 1.
Default – Start address 42000 - Alarm status data for input 1.
Default – Start address 44000 - Relay Contact status data for input 1.
Default – Start address 46000 - Disable status data for input 1.
Default – Start address 48000 - Inhibit Contact status data for input 1.