163
Resolving Problems
If the Positioning Unit ERR LED Lights
Conditions
There is a set value error in the positioning data.
Procedure 1
Using programming tools, check to see if the values in the data registers being used
as the positioning parameter data tables are within the allowable setting range.
Range for positioning data setting
Points to check:
1. Is the value for the startup speed larger than that for the target speed? An error
occurs if the two values are the same, as well.
For the first speed with E point control and P point control, and when carrying
out JOG operation, and home return, a value should be set which is larger than
the startup speed.
2. Has the target speed been set to “0”?
3. Has a data register been set to a negative value?
4. If parameters have been set from an external source, and if operation is being
carried out internally in the PLC, check to make sure the values match those
specified by the design.
Procedure 2
Modify the value out of the range in the program.
Procedure 3
Reset an error by either of the followings;
1. Specify in the program so that the error clear flag (ECLR) goes OFF, ON and
then OFF.
2. By the forced output using WinFPST S/W make the error clear flag (ECLR)
goes OFF, ON and then OFF.
3. Turn OFF once the driver and then PLC and turn ON again PLC and then the
driver.
Type of parameter
Allowable setting
range
Program
specifications
Startup speed (pps)
0 to +1,000,000 [pps]
K0 to K1,000,000
Target speed (pps)
+1 to +1,000,000 [pps]
K1 to K1,000,000
Acceleration/deceleration time (ms)
0 to +32,767 [ms]
K0 to K32,767
If Error Clear Signal (ELOR) is ON, no position operation will be started.
Restart each operation after you clear errors.
Caution
Содержание NX-POSI1
Страница 1: ...Catalog Number s NX70 POSIx NX POSIx NX70 700 Position User Manual ...
Страница 6: ...6 ...
Страница 14: ...14 ...
Страница 22: ...22 ...
Страница 38: ...38 ...
Страница 64: ...64 ...
Страница 79: ...79 Program ...
Страница 82: ...82 Program ...
Страница 106: ...106 Pulse output diagram ...
Страница 107: ...107 Sample Program ...
Страница 110: ...110 ...
Страница 123: ...123 Action of the I O Flag Before and After a Home Return Operation Return Operation ...
Страница 132: ...132 ...
Страница 145: ...145 11 Deceleration Stop and Forced Stop Sample Program In progress Stopping Emergency Stopping Overrun ...
Страница 147: ...147 Pulse output diagram Deceleration stop operation In progress stop ...
Страница 148: ...148 Forced stop operation Emergency stop Overrun ...
Страница 158: ...158 ...
Страница 170: ...170 ...
Страница 178: ...178 Oriental Motor Co Ltd UPK W Series Open collector output stepping drive connection ...
Страница 179: ...179 NX700 PLC External Dimensions 1 System Dimensions mm Motherboard Installation Diagram mm ...
Страница 180: ...180 2 CPU I O Analog Unit Dimensions mm 3 Special Unit Dimensions mm ...
Страница 183: ...183 Program ...
Страница 187: ...187 Program ...
Страница 188: ...188 ...
Страница 194: ...Publication NX700 UM007A PositionA EN December 2010 ...
Страница 195: ......
Страница 196: ...Copyright 2010 RS Automation Co Ltd All rights reserved ...